Skip to content

Fire strategy basics

No law in England or Wales says who may write a fire strategy. The law requires competence: anyone doing design work must have the skills, knowledge, experience and behaviours to make it comply. Clients must take all reasonable steps to check this before appointing. The government plans to make preparing the strategy a function reserved for registered fire engineers.

Last reviewed
Reading time
13 minutes
Related service
Fire Strategy Reports
A curved glass office interior

Does the law say who can write a fire strategy?

No law in England or Wales names the person or profession allowed to write a fire strategy. The title fire engineer is not protected by law either, although the government has said it will legislate to change that.

What the law does require is competence. Part 2A of the Building Regulations 2010 has set competence duties in England since 1st October 2023. Wales has had matching rules in its own Part 2B since 1st July 2026.

Some official guidance goes further for particular documents and gives a registered chartered engineer as an example of a suitable author. The government has also accepted that strategies for higher-risk buildings should be produced by a registered fire engineer. That is not yet law. For what the document itself is, see our guide on what a fire strategy is and our fire strategy reports page.

The competence duty in Part 2A

Part 2A of the Building Regulations 2010 (opens in a new tab), headed Dutyholders and competence, was inserted for England from 1st October 2023 by SI 2023/911. It applies to design work and building work generally, not only to higher-risk buildings.

The general requirement is in regulation 11F(1). Any person carrying out any building work or any design work must have, where the person is an individual, "the skills, knowledge, experience and behaviours necessary". Where the person is not an individual, such as a firm, it must have "the organisational capability". In both cases the test is the ability to carry out the design work so that the building work, if built, "would be in accordance with all relevant requirements".

The relevant requirements listed in regulation 11Q include regulations 7 and 38 and Schedule 1, which contains Part B on fire safety. The same regulation defines design broadly to include drawings, design details, specifications, bills of quantities and calculations prepared for a design. A fire strategy sets out design decisions. It is reasonable to treat it as design work, although the regulation does not mention fire strategies by name.

Regulation 11Q(4) explains what the necessary behaviours include. In summary they are:

  • compliance, including refusing to carry out design work where the building work it relates to cannot be carried out in compliance
  • cooperation with other persons
  • refusing work that is beyond their skills, knowledge or experience and asking for help from other persons where necessary

For a firm, organisational capability means "appropriate management policies, procedures, systems and resources" to make sure individuals meet the competence rules and trainees are appropriately supervised (regulation 11Q(3)). A person in training may do design work if the person who asked them makes sure they are adequately supervised.

What clients, designers and principal designers must do

Regulation 11E(2) puts the first check on whoever makes the appointment, usually the client. Before permitting someone to carry out work, they "must take all reasonable steps" to satisfy themselves that the person meets the competence requirements. The alternative is that the person is in training and supervision has been arranged.

For higher-risk buildings the appointing person must also ask whether a serious sanction has occurred within the 5 years ending on the date of appointment. Serious sanctions include a compliance notice about Part A (structure) or Part B (fire safety), a stop notice, certain convictions and findings under the Inquiries Act.

The duty runs the other way too. Under regulation 11E(6) a person must not accept a request to carry out design work if they do not meet the competence requirements at the time of appointment. If a designer stops meeting them later, regulation 11I requires them to tell the person who asked them to do the work and the principal designer.

Regulation 11K adds a duty that matters for a fire strategy author. A designer doing only part of the design must consider other design work that directly relates to it and report concerns to the principal designer. A fire strategy touches almost every other discipline.

GOV.UK's guidance on design and building work (opens in a new tab) warns that anyone who carries out work beyond their competence or organisational capability "can face enforcement action".

Where there is or will be more than one contractor, the client must appoint a principal designer in writing under regulation 11D. The principal designer must plan, manage and monitor the design work during the design phase.

The principal designer and the fire strategy author can be different people. GOV.UK says a principal designer "is not expected to be an expert in every design specialism". They are expected to know enough about building regulations to assess whether a design will comply.

At Gateway 2 the client signs a competence declaration. BSR's guidance on preparing a building control approval application (opens in a new tab) says it must confirm that the client has taken all reasonable steps to check that the principal designer and principal contractor are competent. It must also confirm that the client has asked those working on the project about serious sanctions in the last 5 years.

The same guidance says the fire and emergency file is often known as a fire strategy. It does not say who must write it. Our guide to the Gateway 2 fire strategy covers what the file must contain.

What official guidance recommends

Several official documents recommend a particular kind of author for the documents and projects they cover. None of them sets a general legal rule for every fire strategy.

Official guidance on who should write fire safety documents
SourceApplies toWhat it says about the authorStatus
Gateway 1 fire statement form guidancePlanning fire statements for relevant buildings in EnglandRecommends a suitably qualified engineer with relevant experience in fire safety, such as a chartered engineer registered with the Engineering Council by the Institution of Fire Engineers. A suitably qualified and competent professional with demonstrable experience is the alternativeRecommendation
London Plan 2021, paragraph 3.12.9Policy D12(B) Fire Statements in LondonShould be a third-party independent, suitably qualified assessor. It gives the same chartered engineer example and the same alternativeAdopted plan
Draft London Plan 2026, paragraph 2.125LondonDefines a competent fire engineer as one registered with the Engineering Council as IEng or CEng and a member of the Institution of Fire Engineers or another fire relevant engineering institutionDraft
DfE Technical Manual, January 2026, section 9.2Fire safety evidence for modern methods of construction on DfE projectsAccepts fire engineering calculations from first principles by a suitably qualified individual chartered through the Engineering Council with a relevant organisation such as the Institution of Fire EngineersEmployer's requirements
HTM 05-02 (2015), paragraphs 1.18 and 1.22Healthcare buildings in EnglandAssumes use by competent persons. For very large and complex projects it recommends a design review by a study team involving one or more fire safety engineersGuidance

The Gateway 1 form also asks for the name, qualifications and experience of the person completing it. Our guides to the Gateway 1 fire statement, London Plan Policy D12 and HTM 05-02 cover each in detail.

The Grenfell recommendations and their status

The Grenfell Tower Inquiry made several recommendations about fire engineers. The government's progress report (opens in a new tab) of September 2026, updated on 2nd October 2026, gives their status.

Inquiry recommendations on fire engineering, status at 2nd October 2026
RecommendationWhat it asks forStatus
Recommendation 10A statutory requirement that a fire safety strategy produced by a registered fire engineer is submitted at Gateway 2 for the construction or refurbishment of any higher-risk building, then reviewed and resubmitted at Gateway 3Accepted in full. In progress
Recommendation 15Recognition and protection of the fire engineering profession by law, with an independent body to regulate it, set membership standards, keep a register and regulate conductIn progress
Recommendation 16Masters courses in fire engineeringIn progress
Recommendation 17An authoritative statement on fire engineeringComplete
Recommendation 18Continuing professional development coursesIn progress

The report also corrects the government's earlier response, which had said a fire safety strategy was already required with building control applications. It states: "This is not correct as a fire safety strategy is not a required document to be submitted as part of an application." It adds that requiring the strategy to be produced by a fire engineer depends on progress on Recommendations 15, 16 and 18, which aim to increase fire engineering capacity.

The government has set up a Fire Engineers Transitional Board. Its members include the Building Safety Regulator, the Engineering Council and the Institution of Fire Engineers. The report says £13 million funding is currently available to UK higher education institutions to increase the capacity of fire engineering professionals.

The report also quotes the Inquiry's Recommendation 8: "Calculating the likely rate of fire spread and the time required for evacuation, including the evacuation of those with physical or mental impairments, are matters for a qualified fire engineer."

The plan to regulate fire engineers

On 17th December 2025 the government published its next steps on fire engineering profession reform (opens in a new tab). It said: "The government will legislate to regulate the title and function of a 'fire engineer'." Setting up the regulator will need primary legislation. Once that legislation is implemented, only registered individuals will be legally permitted to use the title fire engineer or carry out restricted fire engineering functions and activities.

The government accepted the principle that preparing the fire safety strategy should be the central, protected function of a regulated fire engineer. All practising fire engineers, regardless of prior experience or qualifications, will have to demonstrate their competence against the regulator's standards. Existing practitioners will have clear routes to show their competence and transition.

Several points are still open. The government will decide which buildings need a strategy from a regulated fire engineer and how to phase this in beyond the higher-risk building regime. It is still exploring with the devolved administrations whether the framework should be UK-wide or for England alone. In December 2025 it said a public consultation on the details would take place in 2026.

The Fire Engineers Advisory Panel published an authoritative statement (opens in a new tab) on the same day. It says the fire safety strategy is at the heart of a fire engineer's work and should be their central, protected function. It notes there is currently no authoritative definition of a fire safety strategy. In the Panel's view a strategy should include:

  • a description of all building features affected by or relevant to fire
  • how the building is expected to perform in a fire, with the assumptions and uncertainties
  • how the safety systems work together
  • how people, including vulnerable people, will be kept safe
  • a plan to enable fire and rescue service intervention
  • a plan for managing and maintaining fire safety over the life of the building

The Panel describes the fire engineer's role as fundamentally one of integration, linking architects and structural and building services engineers into a whole-building approach. It also says there is no single recognised pathway into fire engineering today. In its view this leads to significant variation in the qualifications and skills of those practising as fire engineers.

Professional registration as the bodies describe it

The Engineering Council (opens in a new tab) says its registrants have chosen to have their expertise independently verified. They can use post-nominal letters to show they hold one of its legally protected titles: Chartered Engineer (CEng), Incorporated Engineer (IEng) or Engineering Technician (EngTech). It says registration is awarded through licensed professional engineering institutions against Engineering Council standards.

The Institution of Fire Engineers (opens in a new tab) says it is licensed by the Engineering Council, which it describes as the regulatory body for the engineering profession in the UK. The IFE says CEng is for those who may be accountable for systems with significant levels of risk. It also has a route for higher-risk buildings that it says may include fire engineers, fire safety consultants, fire risk assessors and those overseeing fire strategy compliance.

The Engineering Council says the Panel's statement aligns closely (opens in a new tab) with its UK Standard for Professional Engineering Competence and Commitment for Higher-Risk Buildings (UK-SPEC HRB). It says that standard defines additional expectations for engineers working on higher-risk buildings.

Registration is voluntary today. It shows that a body has independently verified a person's competence against its standards. It is not, at present, a legal licence to write a fire strategy.

Choosing an author for your project

Nothing in Part 2A limits design work to a named profession. The test in regulation 11F is whether the person has the skills, knowledge, experience and behaviours for that particular design. A fire strategy for a hospital, a tall residential block or an engineered design asks far more than one for a simple extension.

Fire risk assessment is a different task under different law. The Fire Safety Order 2005 (opens in a new tab) applies to occupied premises. Article 18(5) says a person is to be regarded as competent where they have sufficient training and experience or knowledge and other qualities. Our guide to fire strategy and fire risk assessment explains how the two documents differ.

Public buyers do not always limit the role either. A university's 2025 contract for a third-party fire strategy and compartmentation review sought a competent and suitably qualified third party and named a fire engineer or an architect as examples. Where a design departs from the guidance, Approved Document B says fire safety engineering may be the only practical way to achieve a satisfactory standard of fire safety in some complex buildings. Our guide to fire engineered solutions explains that route.

GOV.UK says individuals must be able to demonstrate the full range of skills, knowledge, experience and behaviours for the role they are appointed to. Its examples include completing formal training and providing a portfolio of work detailing relevant experience and knowledge.

The checks below are general professional advice that follows from those duties. They are not an official checklist.

  • Ask for examples of strategies for buildings of the same use, height and complexity.
  • Ask which guidance or codes the author has worked to and how they justified any departures.
  • Check any professional registration claimed with the body that awarded it.
  • On a higher-risk building, ask the serious sanction question that regulation 11E requires for the last 5 years.
  • Ask who will write the strategy and who will answer building control and fire service queries on it.

Where an existing strategy's author or reasoning is unclear, a fire strategy review is a separate check before submission. Designs that depart from the guidance fall under fire engineering. Our guide to fire strategy report cost explains what drives the fee. When you are ready to commission a strategy, our fire strategy reports page sets out what it covers.

Wales and Scotland

Wales has its own competence rules. SI 2025/1320 (opens in a new tab), the Building etc. (Amendment) (No. 2) (Wales) Regulations 2025, came into force on 1st July 2026 and applies in relation to Wales. It inserts Part 2B, Wales Dutyholders and competence, into the Building Regulations 2010. Regulation 11W uses the same competence wording as England's regulation 11F. Part 2B applies to building work generally, not only to higher-risk buildings. See our Wales page and our guide to higher-risk buildings in Wales.

Part 2A and Part 2B do not apply in Scotland, which has its own building standards system. The Scottish non-domestic Technical Handbook says that BS 7974 and the International Fire Engineering Guidelines assume those carrying out or assessing a fire engineering approach have sufficient technical training, knowledge and experience to understand fully the risks involved. See our Scotland page.

Sources

This guide was written from these official sources. Check the current version before relying on any figure.

Common questions

More on this topic.

All fire strategy questions

No law requires that at present in England or Wales. Designers must have the competence the work needs under regulation 11F in England or regulation 11W in Wales. The government has said it will legislate so that preparing the fire safety strategy becomes a protected function of a regulated fire engineer.

Keep reading

Related guides.

Talk to an engineer

Tell us about the building

Send us the drawings, the building type and the stage you are at. We reply the same day with a clear scope, programme and fixed fee.

  • 01Written in-house by the engineer who will defend it to the approver
  • 02Approved Document B, BS 9999, BS 9991 and BS 7974
  • 03Building Control and fire authority engagement handled for you
  • 04Projects of every size, across the UK

Request a quote

Same-day reply

Only used to reply to this enquiry.