Two documents with different jobs
A fire strategy and a fire risk assessment answer different questions at different points in a building's life. The fire strategy is a design document. It explains how the building is designed and built to meet the fire safety requirements of the Building Regulations and how its fire safety measures work together. Our guide on what a fire strategy is covers it in full.
The fire risk assessment is a legal duty for premises in use. Under article 9 of the Fire Safety Order (opens in a new tab) the Responsible Person must make a suitable and sufficient assessment of the risks to which relevant persons are exposed, to identify the general fire precautions needed to comply with the Order. The Order applies in England and Wales. Our fire strategy reports service produces the design document that the assessment later relies on.
The Home Office guide to fire safety in purpose-built blocks of flats (opens in a new tab) explains why both exist. Building Regulations set requirements when a block is designed and built but have no further effect until alterations are proposed. Once the block is occupied, control of fire safety passes to the Housing Act 2004 and the Fire Safety Order.
| Question | Fire strategy | Fire risk assessment |
|---|---|---|
| What it is | A design document explaining how the building meets Part B and how its fire safety measures work together | In the Home Office's words, a methodical, structured examination of the risk from fire to relevant persons in the premises |
| Legal basis | No law defines it. Building control must be satisfied that Part B is met and Approved Document B says any strategy prepared should be handed over under Regulation 38 | Article 9 of the Fire Safety Order in England and Wales. Part 3 of the Fire (Scotland) Act 2005 in Scotland |
| Who is responsible | The client and those carrying out the building work | The Responsible Person, who cannot delegate the legal responsibility |
| When it is produced | During design, then updated when the building is altered or changes use | Once the premises are in use, then reviewed regularly and after significant change |
| What it describes | What should be there and what the design assumes about management | What is there, whether it works and whether it still suits the use |
What the Fire Safety Order requires of the assessment
Article 9 sets three linked duties. The Responsible Person must make a suitable and sufficient assessment, review it regularly to keep it up to date and record it. The review duty applies particularly where there is reason to suspect the assessment is no longer valid or where there has been a significant change, including when the premises undergo significant changes, extensions or conversions. Any changes the review shows are needed must then be made.
The record must be made as soon as practicable after the assessment or review. It must include the findings, the measures taken or to be taken and any group of people identified as especially at risk. Article 11 (opens in a new tab) adds a duty to make, give effect to and record arrangements for the planning, organisation, control, monitoring and review of the preventive and protective measures.
The Responsible Person is defined in article 3 (opens in a new tab). In a workplace it is the employer, where the workplace is to any extent under their control. Elsewhere it is the person in control of the premises in connection with a trade, business or other undertaking. Where the person in control has no such connection, it is the owner.
The Home Office says nobody can choose to make someone the Responsible Person and responsibility for compliance cannot be delegated. In blocks of flats it will typically be the freeholder, the managing agents or a residents' management company. Article 5 (opens in a new tab) puts the same duties on anyone else with any control of the premises for matters within their control.
In buildings with two or more sets of domestic premises the Fire Safety Act 2021 (opens in a new tab) made clear that the Order covers the structure, the external walls including balconies, any common parts and all doors between the flats and the common parts. This took effect in Wales on 1st October 2021 and in England on 16th May 2022. The Home Office says that if you contract out the assessment you must make sure it covers these elements.
What a fire risk assessment contains
The Home Office guide for persons with duties under fire safety legislation (opens in a new tab) says an assessment considers fire hazards and how to prevent fire, the measures that protect people when a fire occurs and the arrangements for fire safety. The protective measures include detection and warning, protected escape routes, emergency lighting and signs. The arrangements cover the fire safety policy, the emergency evacuation plan including personal emergency evacuation plans, fire wardens, drills and testing and maintenance.
The same guide calls the assessment the foundation on which fire safety measures in the premises are built. The Home Office five step checklist (opens in a new tab) for England sets out the stages.
- Fire hazards, such as electrical equipment, smoking, arson, heating, cooking, housekeeping and contractors
- People at risk
- Evaluate and act, including floors and staircases, the number and location of exits and whether fire alarms, fire exit signs, emergency lighting and fire extinguishers are needed
- Record, plan and train. You must complete a fire risk assessment and keep a record of it
- Review the assessment regularly and update it after significant changes, keeping a record of each review and its date
The Home Office flats guide says the outcome should be a suitable action plan of physical and managerial measures, normally prioritised. It says there is no legal requirement to use any particular format for the record and points to PAS 79, a publicly available specification from the British Standards Institution, for more detail on the steps while stressing that many other approaches are equally acceptable. Where a fire risk assessor helps, the Home Office says their name and, where applicable, their organisation should be recorded.
For blocks of flats the same guide describes four types of assessment, from Type 1 (common parts only, non-destructive) to Type 4 (common parts and flats, destructive). It says Type 1 is the basic assessment required to satisfy the Fire Safety Order and will normally be sufficient for most purpose-built blocks. The guide was first written in 2011 and its recording rules predate the 2023 changes described below.
What the fire strategy gives the assessor
The two documents meet at handover. Regulation 38 (opens in a new tab) of the Building Regulations 2010 makes the person carrying out the work give fire safety information to the Responsible Person by completion (or first occupation, if earlier, where the building was empty during the work). Approved Document B (opens in a new tab) says its aim is achieved when the person responsible for the building can understand and implement the fire safety strategy, maintain the fire safety systems and carry out an effective fire risk assessment. Where a fire safety strategy has been prepared, it should be made available to the relevant dutyholder.
The Home Office flats guide says information on the fire safety design is usually contained in a fire safety strategy developed during the building project. It adds that this is particularly important where fire engineering has produced designs that are not code-compliant. It also warns that for most existing blocks of flats such information is unlikely to have been documented.
That is why the assessor needs the strategy. A fire engineered building may rely on an extended travel distance or a management regime that looks wrong to someone who does not know the design. Without the strategy the assessor cannot easily tell a considered design decision from a defect. Where no strategy survives, our guide to retrospective fire strategies explains how one is rebuilt.
How the two documents work together
At completion any strategy goes to the Responsible Person with the rest of the Regulation 38 information. In England since 1st October 2023 the Responsible Person must acknowledge that the information is sufficient for them to understand, operate and maintain the building. Our guide to Regulation 38 covers the pack in detail.
When the Responsible Person changes, article 22A (opens in a new tab) requires the outgoing person to pass on the records of assessments and reviews, the identity of any assessor and any information given under Regulation 38. This is how any fire strategy handed over should follow the building from one Responsible Person to the next. Where several Responsible Persons share a building, the Home Office says each fire risk assessment should align with and complement the others to give a whole building approach.
In a higher-risk building with residential units, article 22B (opens in a new tab) requires the Responsible Person to co-operate with each Accountable Person under the Building Safety Act 2022. The Home Office says this would include sharing the fire risk assessment so that the golden thread and the safety case report are complete. Our guide to Accountable Persons and the golden thread explains both.
The government's consultation on Approved Document B, led by the Building Safety Regulator, proposed that dutyholders consider the content of the fire risk assessment when setting the scope of building works. That is a proposal only. The consultation closed on 1st July 2026 and its outcome was still pending at the time of writing.
After significant changes, extensions or conversions the assessment must be reviewed and the strategy should be brought up to date. Our guide to keeping a fire strategy up to date covers what alterations mean for both documents.
Who carries out each one
The Home Office says Responsible Persons can carry out their own fire risk assessments if they are competent to do so. For larger premises it is common to engage a fire risk assessor and you must record their identity. The assessor must be competent not just generally but for your type of premises and its risks. The Home Office advises giving preference to assessors certificated by a recognised third-party certification body or registered by a professional body.
The legal competence duty for assessors is not yet in force. Section 156 of the Building Safety Act 2022 (opens in a new tab) inserts a new article 9A into the Order, under which the Responsible Person must not appoint a person to assist with making or reviewing an assessment unless that person is competent. Subsection (4), which inserts it, had not been brought into force as at 23rd November 2026. The Home Office section 156 guidance (opens in a new tab) says it will come at a later date and recommends using a competent assessor in the meantime.
Appointing an assessor does not move the liability. The Home Office says the Responsible Person is liable in law if the assessment is not suitable and sufficient. Where an inadequate assessment puts people at risk of death or serious injury, the Responsible Person and the assessor have committed an offence and can be prosecuted.
The fire strategy calls for a different skill set. It is written during design by the fire specialist on the design team and tested by building control. Our guide on who writes a fire strategy covers the competence duties for designers.
What changed on 1st October 2023
Section 156 of the Building Safety Act 2022 amended the Fire Safety Order to strengthen the assessment and the information that flows from it. The Home Office says the new requirements came into force on 1st October 2023. Everything except subsection (4) was commenced on that date in England and in Wales, with subsection (8) commenced in Wales for specified purposes.
| Change | Where it sits | What it means |
|---|---|---|
| Full written record | Article 9(6) and (7) | The assessment and all its findings must be recorded in every case. The old limits, such as recording only where there were five or more employees, no longer apply |
| Fire safety arrangements | Article 11(2) | The arrangements must be recorded in all circumstances |
| Information to residents | Article 21A | In buildings with two or more sets of domestic premises, residents must be given relevant information, including the risks the assessment identified |
| Co-operation | Article 22 | Responsible Persons must take reasonably practicable steps to find each other and share contact details and the part of the premises each covers |
| Handover | Article 22A | Assessment records, the assessor's identity and Regulation 38 information pass to a new Responsible Person |
| Accountable Persons | Article 22B | In a higher-risk building with residential units, Responsible Persons must co-operate with each Accountable Person |
| Assessor competence | Article 9A | Enacted by section 156(4) but not yet in force |
Some fines also rose. The Home Office says certain offences, including failing to provide a copy of the fire risk assessment to an inspector on request, moved from Level 3 (£1,000) to Level 5 (unlimited) for offences after 1st October 2023. Under article 32 (opens in a new tab), a failure that places people at risk of death or serious injury can lead on indictment to a fine, up to two years' imprisonment or both.
Reviews, records and common mistakes
The Fire Safety Order does not specify how often an assessment should be reviewed. The Home Office says your fire risk assessor should advise on the frequency and that an annual review is recognised as good practice for small and simple premises.
A review does not necessarily mean a completely new assessment. A competent person might check that the actions were taken, that nothing has changed in the premises or their management that affects fire risk and that fire safety measures have not deteriorated. The Home Office also says compartmentation should be checked regularly, particularly after works that might penetrate or damage it. Official guidance names these common mistakes.
- Treating a fire sector background or past fire and rescue service experience as proof of competence. The Home Office says neither makes someone a fire safety specialist
- Recommending intrusive Type 2 inspections as a matter of course. The flats guide says the age of a block alone is not generally sufficient to warrant one
- Leaving findings unactioned. The Home Office says significant findings must be actioned within the period specified
Wales and Scotland
In Wales the Fire Safety Order, the Fire Safety Act 2021 changes and section 156 all apply, while the Fire Safety (England) Regulations 2022 apply in England only. The Building Safety (Wales) Act 2026 received Royal Assent on 27th April 2026 and will make further changes to the Order for Wales. Its main provisions had not been commenced when checked in November 2026. Our Wales page covers projects there.
Scotland has its own law. Under Part 3 of the Fire (Scotland) Act 2005 (opens in a new tab) employers and people with control of relevant premises must carry out an assessment of fire risks and review it in line with regulations made under section 57. The Scottish non-domestic Technical Handbook says the fire strategy should preferably support any such assessment. Our Scotland page covers projects there.
If your building has a fire risk assessment and no strategy, a retrospective fire strategy gives the assessor the design record they need. Where a strategy may no longer match the building, a fire strategy review shows the gaps. For new work, our fire strategy report team can quote from your drawings.
Sources
This guide was written from these official sources. Check the current version before relying on any figure.
- Regulatory Reform (Fire Safety) Order 2005, article 9 (official source, opens in a new tab)
- Regulatory Reform (Fire Safety) Order 2005, article 3 (official source, opens in a new tab)
- Regulatory Reform (Fire Safety) Order 2005, article 22A (official source, opens in a new tab)
- Building Safety Act 2022, section 156 (official source, opens in a new tab)
- Fire Safety Act 2021, section 1 (official source, opens in a new tab)
- Fire safety responsibilities under section 156 of the Building Safety Act 2022 (Home Office) (official source, opens in a new tab)
- A guide for persons with duties under fire safety legislation (Home Office) (official source, opens in a new tab)
- Fire safety risk assessment: 5-step checklist (Home Office) (official source, opens in a new tab)
- Fire safety in purpose-built blocks of flats (Home Office guide) (official source, opens in a new tab)
- Approved Document B Volume 2: Buildings other than dwellings (England) (official source, opens in a new tab)
- Building Regulations 2010, regulation 38 (official source, opens in a new tab)
- Check your fire safety responsibilities under the Fire Safety (England) Regulations 2022 (Home Office) (official source, opens in a new tab)