Compartmentation divides a building into fire resisting cells so a fire is held where it starts. In England it is one of the ways requirement B3 of the Building Regulations is met. Fire stopping seals joints and service openings and cavity barriers close concealed spaces. English blocks of flats above 11 metres also need regular fire door checks.

Last reviewed
Reading time
14 minutes
Related service
Fire Strategy Reports
A brick apartment building with balconies

What compartmentation does

Compartmentation divides a building into fire resisting cells. A fire that starts in one cell is held there long enough for people to escape and for firefighters to act. In England the legal requirement is B3 in Schedule 1 to the Building Regulations 2010, with the guidance in Approved Document B (opens in a new tab) Volumes 1 and 2.

Requirement B3(3) says that where reasonably necessary to inhibit the spread of fire within the building, measures shall be taken, to an extent appropriate to its size and intended use. Those measures are sub-division with fire-resisting construction, suitable automatic fire suppression systems or both. B3(4) requires the unseen spread of fire and smoke within concealed spaces in the structure and fabric to be inhibited. In the Secretary of State's view, B3 is met by stable structure, compartmentation, suppression where necessary, protected openings and the inhibition of unseen spread in cavities.

A wall with the right rating does little if a gap at its head, an unsealed service hole or a door that does not close lets fire past. Our fire strategy reports set out the compartmentation for each building and show it on plan.

Where compartment walls and floors are needed

In blocks of flats, paragraph 7.1 of Volume 1 says any floor (unless it is within a flat), any wall separating a flat from another part of the building, any wall enclosing a refuse storage chamber and any wall common to two or more buildings should be compartment walls and floors. Paragraph 3.38 says the wall between each flat and the common corridor should be a compartment wall of minimum REI 30 where the top storey is up to 5 metres above ground and REI 60 otherwise.

For buildings in a non-residential purpose group, paragraph 8.11 of Volume 2 includes every wall needed to keep compartments within the sizes in Table 8.1 and every floor where the top storey is more than 30 metres above ground. In residential (institutional) and residential (other) buildings all floors should be compartment floors (paragraphs 8.8 and 8.10). Our guide to warehouse fire safety deals with industrial and storage buildings.

Compartment walls and floors should form a complete barrier to fire between the compartments they separate and have the fire resistance given in Appendix B Tables B1 and B2 (Volume 1 paragraph 7.5). For blocks of flats Table B2 gives these minimum periods.

Minimum periods of fire resistance for blocks of flats, Approved Document B Volume 1 Table B2 (England)
BuildingHeight of top storey or depth of basementMinimum period
Block of flats without sprinklersUp to 5m30 minutes
Block of flats without sprinklersUp to 11m60 minutes
Block of flats without sprinklersAbove 11mNot permitted
Block of flats with sprinklersUp to 18m60 minutes
Block of flats with sprinklersUp to 30m90 minutes
Block of flats with sprinklersOver 30m120 minutes
Basement storeysUp to 10m deep60 minutes
Basement storeysMore than 10m deep90 minutes

The notes to Table B2 say that for compartment walls separating buildings the period is increased to a minimum of 60 minutes. The not permitted entry reflects paragraph 7.4, which says blocks of flats with a top storey above 11 metres should have sprinklers throughout. Our guide to sprinklers in blocks of flats covers that rule.

Appendix B and parts of Appendix C are marked to be replaced by an amendment, already published, that removes the national classes of fire resistance. Our guide to Approved Document B explains its amendments.

Keeping the compartment line continuous

Volume 2 paragraph 8.4 puts the principle in two parts. Fire resistance should be continuous at the join between elements forming a compartment. Any openings between two compartments should not reduce the fire resistance.

  • Compartment walls between buildings should run the full height of the building in a continuous vertical plane and through any roof space to the underside of the roof (Volume 1 paragraph 7.8).
  • Other compartment walls should run the full height of the storey. In a top storey beneath a roof they should be continued through the roof space (paragraphs 7.10 and 7.11).
  • At a junction with another compartment wall or an external wall the fire resistance should be maintained, with fire-stopping that meets paragraphs 9.24 to 9.29 (paragraph 7.12).
  • A compartment wall should accommodate floor deflection in a fire. In the middle half of a span the deflection may be assumed to be 40mm unless a smaller value can be justified by assessment (paragraph 7.14).

Paragraph 7.20 limits openings in compartment walls and floors to fire doorsets, services that comply with Section 9, refuse chutes of class A1, atria designed to Annexes B and C of BS 9999 and protected shafts. Stairs and service shafts that connect compartments should be protected shafts. The walls or floors around them count as compartment walls or floors (paragraph 7.21).

On 22nd December 2025 the Building Safety Regulator published research by BRE Global (opens in a new tab) on fire-stopping where compartment walls meet three modern roof constructions. The page states that its findings and recommendations do not represent government policy.

Cavity barriers and fire stopping

Volume 1 paragraph 8.2 says cavity barriers should not be confused with fire-stopping details. Paragraph 8.1 explains that cavities provide a ready route for the spread of smoke and flame, which can present a greater danger because the spread is concealed. For the Approved Document a cavity is any concealed space.

Fire-stopping, under paragraph 9.1, keeps the fire resistance of a fire-separating element from being impaired by its joints and service openings. Fire-separating elements include compartment walls and floors, cavity barriers and construction enclosing a protected escape route or a place of special fire hazard.

Cavity barriers and fire-stopping in Approved Document B (England)
QuestionCavity barrierFire-stopping
What it isA construction within a cavity, other than a smoke curtain, that closes the cavity or restricts the movement of smoke or flame within itA seal that closes a joint, imperfect fit or service opening
Where it goesAt the edges of cavities, including around openings. At junctions of cavity walls with compartment floors, compartment walls and other fire resisting walls or door assemblies (paragraph 8.3)Every joint, imperfect fit and opening for services through a fire-separating element (paragraphs 9.1 and 9.24)
Minimum performanceE 30 integrity and I 15 insulation, tested from each side separately (paragraph 8.8)The fire resistance of the element it seals should not be impaired
FixingTightly fitted to a rigid construction and mechanically fixed so that building movement and, in a fire, collapsing services or failed fixings do not make it ineffective (Volume 2 paragraphs 9.15 and 9.16)Reinforced or supported with class A2-s3, d2 or better materials where the unsupported span is greater than 100mm or non-rigid materials are used (paragraph 9.25)

Paragraph 8.4 says it is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment walls should extend to the underside of the floor or roof above.

Paragraph 9.24 says openings for pipes, ducts, conduits or cable should be as few as possible, as small as practicable and fire-stopped, allowing thermal movement for a pipe or duct. Fire-stopping around dampers and smoke control ducts should follow the manufacturer or supplier's installation instructions. For further guidance the Approved Document points to the ASFP Red Book.

Pipes and ducts have their own methods in paragraphs 9.2 to 9.22. In flats, dampers on ducts serving more than one flat should be actuated by both smoke detector controlled release mechanisms and thermal devices (paragraph 9.14).

Fire doors in the design

A fire doorset is the complete assembly as installed, made up of the frame, leaf or leaves, essential hardware, edge seals and glazing. Doors only work if they are closed when a fire starts. Appendix C of Volume 1 sets out how they should be specified.

  • All fire doorsets, including flat entrance doors, should have a self-closing device. The exceptions are cupboards, normally locked service ducts and doors within flats and dwellinghouses (paragraph C5).
  • Where a self-closer would interfere with normal use, the door may be held open by a fusible link, an automatic release on the fire alarm or a door closer delay device (paragraph C6).
  • Unless doors give both integrity and insulation, a maximum of 25 percent of the length of a compartment wall should consist of door openings (paragraph C8).
  • Fire doorsets should carry signs such as fire door keep shut to BS 5499-5 on both sides. Doors to and within flats and dwellinghouses are exempt (paragraphs C11 and C12).

Table C1 sets the rating for each door position. A door to a protected entrance hall or landing in a flat needs E 20 (FD 20) and a door to a protected lobby approach or protected corridor to a stairway needs E 30 Sa (FD 30S). Paragraph C14 names BS 8214 for the specification and maintenance of non-metallic fire doorsets.

Fire door checks in blocks of flats in England

Since the Fire Safety Act 2021, article 6 of the Fire Safety Order (opens in a new tab) says that in a building with two or more sets of domestic premises the Order applies to the structure, external walls and common parts and to all doors between the flats and the common parts. That change took effect on 16th May 2022 in England and on 1st October 2021 in Wales.

The Fire Safety (England) Regulations 2022 came into force on 23rd January 2023. They extend to England and Wales but apply in England only. Regulation 10 (opens in a new tab) sets the fire door duties for responsible persons in buildings with two or more sets of domestic premises and common parts used for evacuation.

Fire door duties under regulation 10 of the Fire Safety (England) Regulations 2022
DutyWhich buildingsHow often
Tell residents that fire doors should be kept shut when not in use, that self-closing devices should not be tampered with and that faults or damage should be reported immediatelyTwo or more sets of domestic premises with common parts used for evacuation, of any heightNew residents as soon as reasonably practicable and all residents within each 12 months
Use best endeavours to check the fire doors at the entrances of individual flatsAbove 11 metres in heightAt least every 12 months
Check any fire doors in communal areasAbove 11 metres in heightAt least every 3 months
Keep a record of the flat entrance door checks, including the steps taken to gain access where it was not grantedAbove 11 metres in heightFor each 12 month period

The checks must include making sure the self-closing devices work. Height is measured to the top storey in accordance with Appendix D to Approved Document B. The GOV.UK guidance Check your fire safety responsibilities (opens in a new tab) describes this as typically a building of five storeys or more.

The fire door guidance (opens in a new tab), updated 8th August 2025, says the checks should be simple and basic and should not need a specialist. Caretakers, managing agents and maintenance staff should be able to do them. Repairs or replacement must be undertaken by a competent contractor as soon as reasonably practicable.

A check covers the door, frame, glazing, hinges, letterbox, any intumescent strips and smoke seals and the self-closer. The gap should never be more than 4mm except at the bottom of the door. Riser and plant room doors should also be checked at least every three months.

The same guidance says the regulations are not meant to make existing flat entrance doors meet the current standards for new blocks. A door that met the standard when it was built or made will continue to give adequate protection if it is undamaged and the gaps to the frame are not too large. Whether a door type is suitable is a matter for the fire risk assessment, not regulation 10, as our guide to fire strategy and fire risk assessment explains.

Where a leaseholder will not give access, the guidance says a court order can be obtained in the event of an impasse and recommends that new leases include the right of access. A breach is a criminal offence if it places relevant persons at risk of death or serious injury in the event of fire.

What Grenfell showed about doors and compartmentation

The Grenfell Tower Inquiry Phase 2 report, Volume 1 (opens in a new tab) found that the front doors installed by the tenant management organisation (TMO) in 2011 and 2012 did not meet the fire resistance standards suggested by Approved Document B because the TMO had failed to specify the correct fire safety standard when ordering them. It found that many self-closing devices on the front doors failed to work effectively and some were missing entirely. The TMO did not institute an effective inspection and maintenance programme for them despite an Enforcement Notice issued by the London Fire Brigade in late 2015. The report also identified as needing urgent attention the assumption that compliance with functional requirements B3 and B4 will provide a high degree of compartmentation and so make evacuation of the building unnecessary.

The government's September 2026 progress report (opens in a new tab) lists the related recommendation as Recommendation 7 (Inquiry reference 113.13). The Inquiry recommended that the assumption of effective compartmentation be reconsidered when Approved Document B is revised. The government accepted this in full and lists it as in progress. The report says the Building Safety Regulator's consultation on Approved Document B, published with MHCLG, closed on 1st July 2026 with more than 500 responses and that recommendations are expected by March 2027.

The 2022 fire door duties came out of the Inquiry's first phase. The fire door guidance says the regulations implement the majority of the Phase 1 recommendations made to government that require a change in the law. For designers the lesson is practical. A compartmentation strategy should say what has to be kept closed, sealed and maintained and who checks it.

Existing buildings, alterations and handover

In an occupied block, compartmentation is checked through the fire risk assessment. The Local Government Association guide Fire safety in purpose-built blocks of flats (opens in a new tab), hosted on GOV.UK, describes four types of assessment from Type 1 (common parts, non-destructive) to Type 4 (common parts and flats, destructive). A Type 1 inspection will normally be sufficient unless there is reason to expect serious deficiencies such as inadequate compartmentation or poor fire stopping. Within flats the extent of fire stopping can only be established through destructive inspection.

The same 2011 guide, which its cover note says should be viewed as no longer comprehensive, lists alterations that harm fire safety. They include a flat entrance door changed without a suitably fire-resisting and self-closing replacement and riser walls breached for new drains and not fire-stopped. Under regulation 3 of the Building Regulations 2010 (opens in a new tab) work of this kind can be a material alteration if it would leave the building not complying with a relevant requirement, such as B1, B3, B4 or B5, where it did before.

Our guide to keeping a fire strategy up to date covers alterations. Where the original records are missing, see our guide to retrospective fire strategies.

For new buildings the record starts at handover. Under Section 17 of Volume 1 the as-built plan should show fire resisting construction and the location of fire-separating elements, including cavity barriers in walk-in spaces (paragraph 17.4). For complex buildings the records should include all passive fire safety measures, including compartmentation, cavity barriers, fire doorsets, dampers and fire shutters (paragraph 17.7). Our guide to Regulation 38 covers the full handover duty.

Wales and Scotland

The Fire Safety Order extends to Wales and the Fire Safety Act 2021 change bringing structure and flat entrance doors within it took effect there on 1st October 2021. The quarterly and annual door checks are not a statutory duty in Wales because the Fire Safety (England) Regulations 2022 apply in England only. Building work in Wales follows the Welsh Approved Document B (opens in a new tab). See our Wales page for projects there.

In Scotland, Standard 2.1 of the non-domestic Technical Handbook (opens in a new tab) requires fire and smoke to be inhibited from spreading beyond the compartment of origin until occupants have had time to leave it. It does not apply to domestic buildings, where separation is covered by Standard 2.2. Duties in occupied buildings fall under Part 3 of the Fire (Scotland) Act 2005 (opens in a new tab) and the Fire Safety (Scotland) Regulations 2006. See our Scotland page for projects there.

Wherever the building is, compartmentation has to be designed, built and then kept. Our fire strategy reports set out the compartment lines, the fire-stopping and door provisions they depend on and the information the building will need in occupation.

Sources

This guide was written from these official sources. Check the current version before relying on any figure.

Common questions

More on this topic.

All fire strategy questions

Fire stopping seals joints, gaps and service openings through a fire-separating element so its fire resistance is not impaired. A cavity barrier is a construction inside a concealed space that closes the cavity or restricts smoke and flame movement within it. Approved Document B says the two should not be confused.

Keep reading

Related guides.

Talk to an engineer

Tell us about the building

Send us the drawings, the building type and the stage you are at. We reply the same day with a clear scope, programme and fixed fee.

  • 01Written in-house by the engineer who will defend it to the approver
  • 02Approved Document B, BS 9999, BS 9991 and BS 7974
  • 03Building Control and fire authority engagement handled for you
  • 04Projects of every size, across the UK

Request a quote

Same-day reply

Only used to reply to this enquiry.

We reply the same day.