Skip to content

Regulations and design guidance

In England, Approved Document B says new blocks of flats with a top storey more than 11 metres above ground should have a sprinkler system throughout, provided within the flats, to BS 9251. The threshold fell from 30 metres in an amendment that took effect on 26th November 2020, which also added wayfinding signage for the fire service.

Last reviewed
Reading time
11 minutes
Related service
Fire Strategy Reports
A tall white apartment building with glass balconies

What the 11 metre rule says

In England, Approved Document B Volume 1 (opens in a new tab) paragraph 7.4 says blocks of flats with a top storey more than 11 metres above ground level should be fitted with a sprinkler system throughout the building in accordance with Appendix E. The note to the paragraph explains what throughout means for flats. Sprinklers should be provided within the individual flats. They do not need to be provided in common areas such as stairs, corridors or landings when these areas are fire sterile.

Approved Document B is approved by the Secretary of State and gives practical guidance on how to meet the Building Regulations 2010 in England. The Approved Documents note that there may be other ways to comply with the requirements. For sprinklers, the government's FAQ on the guidance sets out the evidence behind the recommendation in some detail. The GOV.UK page (opens in a new tab) marks the guidance as applying to England.

Sprinklers are one of the first questions in a fire strategy report for a block of flats. They fix plant space, water storage and the routes for pipework through the building. They need settling at concept stage rather than at technical design.

How the height is measured

The 11 metres is measured to the top storey, not the roof. Diagram D6 measures from the upper floor surface of the top floor to ground level on the lowest side of the building. It excludes roof-top plant areas and any top storeys consisting exclusively of plant rooms.

On a sloping site the lowest side of the building sets the height. The entrance level on the high side is not the reference. A top storey that holds only plant rooms is excluded, while a top storey with any other accommodation counts.

The same diagram sets the 18 metre threshold for second staircases in paragraph 3.30(b). The top floor level is therefore one of the most important numbers on a residential scheme. Our guide to second staircases over 18 metres covers that rule.

When the rule came in and the transition

The trigger height fell from 30 metres to 11 metres through the May 2020 amendments (opens in a new tab) to Approved Document B. The booklet says the changes take effect on 26th November 2020 for use in England. It made two changes. One reduced the sprinkler trigger height. The other added a new recommendation for floor identification and flat indication signage in blocks of flats with storeys over 11 metres.

Key dates for the 2020 sprinkler and wayfinding amendment (England)
DateWhat happened
5th September 2019Consultation on sprinklers and other fire safety measures in new high-rise blocks of flats opened
28th November 2019Consultation closed
26th May 2020May 2020 amendments to Approved Document B Volumes 1 and 2 added to GOV.UK
26th November 2020Amendment took effect in England and the volumes incorporating the 2020 amendments were added to GOV.UK
29th January 2021Work under a notice or full plans given before 26th November 2020 had to start before this date to stay under the 2019 edition

The transitional rule is set out in the booklet. The 2019 edition continued to apply where a building notice or an initial notice had been given before 26th November 2020. It also applied where full plans had been deposited with a local authority before that day. The building work also had to have started before that day or be started before 29th January 2021. Work outside those conditions falls under the amended guidance.

The consultation had asked about a transition period of six months. Of the respondents, 48 percent agreed with it. The cut-off in the booklet was the start of work before 29th January 2021.

Why the threshold is 11 metres

The 2019 consultation (opens in a new tab) received 184 responses. Of those answering the first question, 97 percent agreed the threshold should be reduced. Of the 171 answers on the new level, 40 percent recommended 11 metres or similar and only 25 percent recommended 18 metres.

The government response (opens in a new tab) gives the reasoning. It says the government heard from respondents that the expected limit of external firefighting capacity is around 11 metres. Its analysis estimated that up to 50 percent of new blocks of flats with a top storey between 11 and 30 metres were already including some form of sprinkler system. Several respondents noted that 11 metres would align with incoming guidance in Scotland. The impact assessment compared the change with doing nothing and with a threshold of 18 metres.

The government's Approved Document B FAQ (opens in a new tab) sets out the case for sprinklers in flats. It cites BRE research estimating reductions in deaths and injuries of 90 percent and 61 percent where sprinklers are provided in purpose built flats. It also cites Welsh analysis giving 90 percent and 62 percent.

Designing the system: standards, reliability and trade-offs

Appendix E sets the design standard. Residential buildings should follow BS 9251. Non-residential buildings and residential buildings outside the scope of BS 9251 should follow BS EN 12845, with the relevant hazard classification and the additional measures to improve reliability and availability described in Annex F of that standard.

Where sprinklers are required, Appendix E says they should be provided throughout the building or separated part, unless they act as a compensatory feature to address a specific risk. Any system installed to satisfy Part B should have additional measures to improve reliability and availability. It is to be regarded as a life safety system.

That status affects the water supply, the pumps, the power and the way the system is monitored and maintained. Each of those choices belongs in the fire strategy. They should then be carried into the fire safety information handed over at completion under Regulation 38.

Sprinklers often lead to questions about relaxing other measures. The FAQ says whether other fire protection can be reduced is a matter for the designer and the relevant building control body to consider. It warns that any such proposal may mean upgrading the sprinkler specification and the duration of water supplies. Another FAQ answer considers whether higher fire resistance to walls and floors could replace sprinklers over 11 metres. It does not offer that as an alternative and sets out the evidence for sprinklers instead.

Wayfinding signage for the fire service

The second half of the 2020 amendment is signage. Paragraph 15.13 says floor identification signs and flat indicator signs should be provided in a block of flats with a top storey more than 11 metres above ground level. Their purpose is to help the fire service identify each floor. Paragraphs 15.14 to 15.16 set out the detail.

  • Signs on every landing of a protected stairway.
  • Signs in every protected corridor, lobby or open access balcony into which a firefighting lift opens.
  • Sans serif text at least 50 millimetres high, with the floor numeral at least 75 millimetres high.
  • Visible from the top step of a firefighting stair and, where possible, from inside a firefighting lift.
  • Mounted between 1.7 metres and 2 metres above floor level.
  • Readable in low level lighting or when lit with a torch.
  • Floor signs worded Floor X, with the floor closest to mean ground level shown as Floor 0 or Ground Floor.
  • Flat indicator signs showing the range of flat numbers with the lowest first, no more than 50 millimetres below the floor sign and with arrows where flats lie in more than one direction.

The government chose not to extend the signage below 11 metres. Its response said it did not believe there would be significant benefit, as such a building could often be less than three storeys.

Two later additions sit beside the signs. The 2022 amendments added paragraph 15.17, which recommends an evacuation alert system to BS 8629 in blocks of flats with a top storey over 18 metres above ground. The government's consultation page records that change as made on 1st June 2022. The same amendments added paragraph 15.19, which recommends secure information boxes in blocks of flats with a top storey more than 11 metres above ground. Our guide to evacuation strategies explains how alert systems are used.

Extensions, change of use and existing buildings

Approved Document B is guidance on meeting the Building Regulations when building work is done. Paragraph 7.4 is written for new blocks of flats and does not ask for sprinklers to be retrofitted into existing blocks where no work is planned. The FAQ and the regulations show how it can reach work to existing buildings.

Adding storeys is the common case. FAQ 26 covers a new floor that takes an existing building over 11 metres. It says each case must be considered on its own merits. It adds that where storeys are added, some work on the original part of the building is likely to be necessary. In the majority of cases, it says, sprinkler protection will be necessary in any newly formed accommodation above the 11 metre trigger height. It points to regulation 4(1) and to regulation 4(3), under which the level of fire protection in the building as a whole is to be made no worse.

Upward extensions are where cost plans can fall short. A budget that covers the new floors alone leaves no room for the questions building control will ask about the floors below. Settle the scope for the existing building before the structure is fixed.

A material change of use is the other route. Under regulation 6 (opens in a new tab) of the Building Regulations 2010 in England, a material change of use of the whole of a building means carrying out any work needed for the building to comply with requirements B1, B2, B3, B4(2) and B5, among others. Paragraph 7.4 sits in the guidance on B3, internal fire spread of the structure, for flats. Our guide to fire strategy for a change of use covers conversions in more detail.

Care homes and specialised housing

A separate recommendation covers care homes. Since 2nd March 2025, Approved Document B Volume 2 (opens in a new tab) paragraph 2.46 has said care homes should be fitted with a sprinkler system throughout the building in accordance with Appendix E. The paragraph carries no height limit. The 2022 consultation had proposed sprinklers in new care homes regardless of building height.

The 2025 amendment booklet (opens in a new tab) set the transition. The previous edition continued to apply where a notice or full plans application was given before 2nd March 2025 and the work had started and was sufficiently progressed before that day. It also continued to apply where the work started and was sufficiently progressed within six months beginning on that day.

Specialised housing is still under review. The Building Safety Regulator's consultation on its review of Approved Document B (opens in a new tab), published with MHCLG, opened on 25th March 2026 and closed on 1st July 2026. It costed sprinklers in specialised housing with care at £19.2 million over a 10 year period and in all specialised housing at £79 million. It concluded that increased alarm provisions provide the best value for money improvement to life safety in those building types. These are proposals only. The government's September 2026 Grenfell progress report says recommendations are expected by March 2027.

Sprinklers in Wales and Scotland

Both nations apply sprinklers to new flats without a height threshold. The table compares the three rules.

Sprinklers in new residential buildings across Great Britain
NationRuleIn forceHeight threshold
EnglandApproved Document B paragraph 7.4: blocks of flats should have sprinklers throughout26th November 2020Top storey more than 11 metres
WalesRegulation 37A: automatic fire suppression on the erection or material change of use of dwelling-houses, flats, care homes and rooms for residential purposes1st January 2016None
ScotlandBuilding standard 2.15 extended to buildings containing flats or maisonettes1st March 2021None

In Wales, the Domestic Fire Safety (Wales) Measure 2011 (opens in a new tab) was passed to require automatic fire suppression systems in new residential premises. It is delivered through regulation 37A of the Building Regulations 2010 as they apply in Wales. That has applied in full since 1st January 2016. It covers dwelling-houses and flats, care homes and rooms for residential purposes other than hostels, hotels, prisons and hospitals. Children's care homes were added from 17th December 2024.

Wales adopted the 11 metre wayfinding signage from 20th December 2025 through an amendment to its own Approved Document B (opens in a new tab). The same amendment added evacuation alert systems over 18 metres. It does not apply where a notice or full plans were given and the work started before that day or within six months beginning with it. Our guide to fire strategy in Wales covers the Welsh rules in full.

In Scotland, the Building (Scotland) Amendment Regulations 2020 (opens in a new tab) came into force on 1st March 2021. They extended building standard 2.15 to buildings containing flats or maisonettes, social housing dwellings and shared multi-occupancy residential buildings, with no height threshold. From 6th April 2026 a further change extended it to traditionally constructed residential buildings with 15 or more rooms used for sleeping accommodation.

Our guide to Scottish Building Standards Section 2 explains the Scottish fire standards. Wherever the building is, sprinklers are easiest to coordinate when they are designed in from the start. Our fire strategy reports set out the sprinkler, signage and alarm provisions for each block and the standard each one follows.

Sources

This guide was written from these official sources. Check the current version before relying on any figure.

Common questions

More on this topic.

All fire strategy questions

Not when those areas are fire sterile. Approved Document B says sprinklers should be provided within the individual flats and do not need to be provided in common stairs, corridors or landings that are fire sterile.

Keep reading

Related guides.

Talk to an engineer

Tell us about the building

Send us the drawings, the building type and the stage you are at. We reply the same day with a clear scope, programme and fixed fee.

  • 01Written in-house by the engineer who will defend it to the approver
  • 02Approved Document B, BS 9999, BS 9991 and BS 7974
  • 03Building Control and fire authority engagement handled for you
  • 04Projects of every size, across the UK

Request a quote

Same-day reply

Only used to reply to this enquiry.

We reply the same day.