What the combustible materials ban requires
The ban is regulation 7(2) of the Building Regulations 2010 (opens in a new tab). In England it requires building work to be carried out so that materials which become part of an external wall or specified attachment of a relevant building are of European Classification A2-s1, d0 or A1.
It was introduced by the Building (Amendment) Regulations 2018 (opens in a new tab), made on 28th November 2018 and in force from 21st December 2018. The government's 2018 FAQ (opens in a new tab) says the ban is stricter than the definition of limited combustibility. Products classed only as materials of limited combustibility do not comply.
A separate rule, regulation 7(1A), bans relevant metal composite material from the external wall or specified attachments of any building, whatever its height. It has applied in England since 1st December 2022. The definition covers panels or sheets no more than 10mm thick with two or more metal layers and a substantial layer with a gross calorific value of more than 35 MJ/kg. Our fire strategy reports record how each external wall material meets these rules.
The ban does not replace requirement B4. Approved Document B Volume 1 paragraph 10.20 says the provisions of regulation 7 apply in addition to requirement B4. The potential impact of products in or on the walls should be carefully considered with regard to their number, size, orientation and position.
Which buildings count as relevant buildings?
In England a relevant building under regulation 7(4) has a storey at least 18 metres above ground level and contains one or more dwellings, an institution or a room for residential purposes. Roof-top plant areas and storeys consisting only of plant rooms are not counted. Height is measured from the lowest ground level adjoining the outside of the building to the top of the floor surface of the storey.
A note to Approved Document B Volume 1 paragraph 10.14 says this includes student accommodation, care homes, sheltered housing, hospitals, dormitories in boarding schools, hotels, hostels and boarding houses.
This is not the same as the higher-risk building test under the Building Safety Act 2022 in England. GOV.UK says that in general a higher-risk building is at least 18 metres tall or has at least seven storeys and contains at least two residential units or is a hospital or care home. Our guide to what is a higher-risk building covers that test.
The external wall definition and the exemptions
Regulation 2(6) (opens in a new tab) defines the external wall widely. It includes anything located within any space forming part of the wall, any decoration or other finish applied to its external surface and any windows and doors in it. It also includes any part of a roof pitched at more than 70 degrees to the horizontal where that part adjoins a space within the building to which people have access, other than access only for repairs or maintenance.
Specified attachments are balconies attached to an external wall, solar panels attached to an external wall and solar shading devices. A solar shading device attached no more than 4.5 metres above ground level is excluded. The 2018 FAQ adds that internal plasterboard and sheathing boards are not considered internal finishes and so are included in the definition of the external wall.
The same FAQ confirms that masonry cavity walls are caught. Conventional curtain walling of mullions, transoms and glazing can be considered as a window frame. Spandrel panels and other opaque insulated panels in curtain walls are not exempt. Regulation 7(3) lists the items the ban does not apply to in England.
- Cavity trays used between two leaves of masonry
- Any part of a roof connected to an external wall, other than a roof pitched at more than 70 degrees that counts as part of the wall
- Door frames and doors
- Electrical installations and fibre optic cables
- Insulation and waterproofing materials used below ground level or up to 300mm above it
- Intumescent and fire stopping materials where they are necessary to meet Part B
- Membranes
- Seals, gaskets, fixings, sealants and backer rods
- Components of a solar shading device, other than those whose primary function is to shade or deflect sunlight such as the awning curtain or slats
- Thermal break materials where they are necessary to meet the thermal bridging requirements of Part L
- Window frames and glass
- The top horizontal floor layer of a balcony if it is Class A1fl or A2fl-s1 and the entire layer has an imperforate substrate under it
An exemption does not mean any material will do. Asked whether any material can be used for an exempt component regardless of its combustibility, the 2018 FAQ answers no. Regulation 7(2) applies in addition to requirement B4.
Approved Document B Volume 1 paragraph 10.21 adds detail. Membranes above ground should achieve a minimum of class B-s3, d0. Window spandrel panels and infill panels must comply with regulation 7(2). Thermal breaks should not span two compartments. Shop front signs and similar attachments are not covered by regulation 7(2).
What changed in 2022?
The Building etc. (Amendment) (England) Regulations 2022 (opens in a new tab) were made on 1st June 2022 and came into force on 1st December 2022. They updated the reaction to fire classification to the 2019 publication of BS EN 13501-1 and banned relevant metal composite material on all buildings. They also added solar shading devices to the list of specified attachments.
The same regulations added the exemptions for fibre optic cables, solar shading components, the 300mm insulation and waterproofing allowance and balcony floor layers. The relevant building definition was amended so that the prohibition in regulations 6(3) and 7(2) now applies to hotels, hostels and boarding houses. They also lowered the height at which B4(1) applies on a material change of use of the whole building from 15 metres to 11 metres, through regulation 6(1)(c).
The 2022 changes do not apply where a building notice or initial notice was given or full plans were deposited before 1st December 2022 and the work started before that day or within six months beginning on that day.
The government response to the review (opens in a new tab) records that 44 percent of respondents disagreed with cutting the ban threshold to 11 metres. The government said it would retain the ban at 18 metres and amend Approved Document B to introduce new statutory guidance for buildings between 11 and 18 metres.
Approved Document B guidance for buildings between 11 and 18 metres
Below 18 metres regulation 7(2) does not apply. Approved Document B still makes recommendations, which are guidance rather than law. Since the 2022 amendments they are tighter for residential buildings above 11 metres. The table sets out the Volume 1 position for residential purpose groups 1 and 2 in England.
| Height | External surfaces (Table 10.1) | Insulation and filler (para 10.7) | Balconies (para 10.10) |
|---|---|---|---|
| Storey at least 18 metres in a relevant building | Regulation 7(2) applies: A2-s1, d0 or A1 | Regulation 7(2) applies and prevails | Regulation 7(2) applies to balconies as specified attachments |
| Above 11 metres, below the regulation 7(2) test | Class A2-s1, d0 or better at any distance from the relevant boundary | Class A2-s1, d0 or better where a storey is 11 metres or more | Either only A1 or A2-s1, d0 materials with listed exceptions or an REI 30 imperforate soffit in A2-s1, d0 materials, with 300mm A2-s1, d0 bands where B-s1, d0 or worse materials cross a compartment boundary |
| 11 metres or less | Class B-s3, d2 or better within 1000mm of the boundary. No provisions at 1000mm or more | No 11 metre recommendation | No 11 metre recommendation |
Paragraph 10.7 covers insulation and filler materials such as the core materials of metal composite panels, sandwich panels and window spandrel panels. Gaskets, sealants and similar items are excluded, as are masonry cavity walls that comply with Diagram 8.2. The Volume 2 equivalents are Table 12.1 and paragraphs 12.7 and 12.11.
Paragraph 10.6 applies to any building with a storey 18 metres or more, not just residential ones. Insulation and filler materials there should be class A2-s3, d2 or better. Take an office building over 18 metres with no dwellings or residential rooms. It is outside the ban and paragraph 10.6 is the recommendation its insulation works to.
Under paragraph 10.3 the external walls of buildings outside regulation 7(4) can either follow paragraphs 10.5 to 10.9 or meet the performance criteria in BRE report BR 135 using full-scale test data from BS 8414-1 or BS 8414-2.
Note 3 to Table 10.1 accepts timber cladding at least 9mm thick where class C-s3, d2 is the recommendation. The Approved Document B FAQ (opens in a new tab) says that allowance was based on experiments with flat timber planks over a plasterboard substrate. Our guide to fire safety in timber buildings covers the research that has followed.
Work to existing buildings and changes of use
The ban is not limited to new buildings. The 2018 FAQ says it applies to any building work carried out in or on a building in scope. Materials already in the wall that are not being replaced are not covered, unless there is a change of use. Care is still needed so that the building is no less compliant than before the work, for example where a cavity barrier is disturbed.
During remediation the FAQ says materials which are retained and are not impacted by remediation activity are unlikely to be considered to become part of the external wall. It is for building control bodies to assess compliance and each project should be discussed with the relevant one.
A material change of use described in regulation 5(k) brings the whole wall into question. In England regulation 6(3) (opens in a new tab) requires the work necessary to ensure any external wall or specified attachment only contains materials of A2-s1, d0 or A1, with the regulation 7(3) items excluded. Approved Document B paragraph 10.17 says the external walls must be investigated and, where necessary, work must be carried out. Our guide to fire strategy for a change of use covers the wider requirements.
Where an older building has no reliable record of its wall build-up, a retrospective fire strategy can bring the known information together and show what still needs investigating.
Existing blocks of flats: FRAEWs and PAS 9980
For occupied buildings in England, GOV.UK says the Fire Safety Act 2021 makes it clear that a fire risk assessment must include the building's structure and external walls, including cladding, insulation, balconies and windows. All residential buildings with two or more flats must have a fire risk assessment.
A fire risk appraisal of external walls (opens in a new tab) (FRAEW) is a detailed assessment of the risk of fire spreading through a building's external wall system. It is usually needed when the fire risk assessor has concerns, for example where combustible materials have been identified. An FRAEW may be needed for blocks of flats of any height. Masonry buildings are less likely to need one. Their construction would still need to be confirmed as brick or masonry and not, for example, brick slip over combustible insulation.
PAS 9980:2026 has replaced PAS 9980:2022. The GOV.UK FRAEW guidance (opens in a new tab), published on 14th September 2026, says the updated version does not significantly change how risk is assessed. An FRAEW done under PAS 9980:2022 should continue to be valid until it needs to be reviewed or updated. FRAEWs should be carried out by a suitably qualified specialist using the PAS 9980:2026 methodology. GOV.UK describes four possible outcomes.
- Low risk: no remediation work is needed
- Tolerable risk: no remediation work is needed
- Medium risk: action is needed to reduce the risk to an acceptable level
- High risk: remediation work is strongly recommended
An EWS1 certificate is not a government or regulatory document and is not a safety certificate. Mortgage lenders decide when one is needed.
On remediation, the government's Remediation Acceleration Plan (opens in a new tab) for England, published on 2nd December 2024, says it aims that "by the end of 2029 all 18m+ (high-rise) buildings with unsafe cladding in a government funded scheme will have been remediated". That is a target, not a legal requirement. On 17th July 2025 the government said it would legislate to require landlords to remediate unsafe cladding by the end of 2029 on buildings of 18 metres or more and by the end of 2031 on buildings of 11 to 18 metres. The Building Safety (Remediation of Unsafe Cladding etc) Bill was introduced to Parliament on 14th October 2026 to create a legal duty to assess and remediate residential buildings in England over 11 metres or with at least five storeys. It was at committee stage in the House of Commons in November 2026.
Wales and Scotland
Wales has its own version of regulation 7, in force there from 13th January 2020 under SI 2019/1499. It uses the same 18 metre threshold as England and requires materials of a minimum European Classification A2-s1, d0 or A1. From 20th December 2025 SI 2025/704 (W. 119) (opens in a new tab) added the ban on relevant metal composite material, the fibre optic, 300mm, solar shading and balcony floor exemptions and hotels, hostels and boarding houses.
In Wales the 11 metre figure is guidance. The Welsh amendment slip to Approved Document B (opens in a new tab), with effect from 20th December 2025, adds Volume 2 paragraph 13.8. It says insulation products and filler materials in residential buildings with a storey 11 metres or more should be class A2-s1, d0 or better. Our guide to fire strategy in Wales covers the rest of the Welsh regime.
Scotland has banned combustible cladding at a lower height since 1st June 2022. The Building (Scotland) Amendment Regulations 2022 (opens in a new tab) require materials in an external wall cladding system or specified attachment of a relevant building to be of European Classification A2-s1, d0 or A1. A relevant building there has a storey at a height of 11 metres or more above the ground and contains a dwelling, a place of assembly, entertainment or recreation, a hospital, a residential care building or sheltered housing complex or a shared multi-occupancy residential building. SSI 2025/312 (opens in a new tab) added hotels, guest houses, boarding houses and hostels from 6th April 2026.
The Scottish ban covers the external wall cladding system, not the load-bearing structure. Clause 2.7.1 of the Non-domestic Technical Handbook (opens in a new tab) says external wall cladding systems "mean non load-bearing components attached to the buildings structure", with examples including timber panels and weather boarding. It says sheathing or backing board "attached to and forming part of the elements of structure of the building are not considered to form part of the external wall cladding system". It adds that "where combustible sheathing or backing board is proposed in any building with a storey 11 m or more above the ground, a large scale facade fire test should be carried out".
Clause 2.7.0 links the 11 metre height to the reach of a fire and rescue service ground mounted water jet. Our guide to Scottish Building Standards Section 2 covers the other fire standards.
| Point | England | Wales | Scotland |
|---|---|---|---|
| Height trigger for the ban | Storey at least 18 metres | Storey at least 18 metres | Storey 11 metres or more |
| What the ban covers | External wall and specified attachments | External wall and specified attachments | External wall cladding system and specified attachments |
| Hotels, hostels and boarding houses | From 1st December 2022 | From 20th December 2025 | From 6th April 2026, with guest houses |
| Metal composite material on any building | Relevant metal composite material banned from 1st December 2022 | Relevant metal composite material banned from 20th December 2025 | Highly combustible metal composite material banned (regulation 8(5)) |
| 11 metre recommendations | Approved Document B Volume 1 Table 10.1 and paragraphs 10.7 and 10.10 | Welsh Approved Document B Volume 2 Table 13.1 and paragraphs 13.8 and 13.12 | The ban itself applies from 11 metres |
What may change next in England
The Building Safety Regulator's consultation on a review of Approved Document B (opens in a new tab), published with MHCLG, ran from 25th March 2026 to 1st July 2026. It proposed revised guidance on external wall systems and balconies and a review of the scope of the ban. One proposal is an exemption for laminated glass balustrades with a total thickness of more than 17.5mm but no more than 26mm. Changes to regulations 2(6) and 7(3) would need a new statutory instrument.
The proposed guidance would set recommendations for all buildings of any height and remove deemed-to-satisfy provisions. The government's September 2026 progress report (opens in a new tab) says more than 500 responses were received and recommendations are expected by March 2027. These remain proposals only. Our guide to Approved Document B follows the review.
On a current project, design to the rules in force and record the reasoning for each wall component. If you need the external wall position set out for building control, a lender or a fire risk assessor, our fire strategy reports service can help. Contact us with the elevations and wall specifications.
Sources
This guide was written from these official sources. Check the current version before relying on any figure.
- Building Regulations 2010, regulation 7 (official source, opens in a new tab)
- Building Regulations 2010, regulation 2 (official source, opens in a new tab)
- Building Regulations 2010, regulation 6 (official source, opens in a new tab)
- The Building (Amendment) Regulations 2018 (official source, opens in a new tab)
- The Building etc. (Amendment) (England) Regulations 2022 (official source, opens in a new tab)
- Building (Amendment) Regulations 2018: Frequently Asked Questions (official source, opens in a new tab)
- Government Response: Review of the Ban on the Use of Combustible Materials (official source, opens in a new tab)
- Approved Document B Volume 1: Dwellings (official source, opens in a new tab)
- Understanding Fire Risk Appraisals of External Walls in Blocks of Flats (official source, opens in a new tab)
- The Building (Scotland) Amendment Regulations 2022 (official source, opens in a new tab)
- Building Standards Technical Handbook April 2026: Non-domestic (official source, opens in a new tab)
- Review of Approved Document B: Fire Safety (consultation) (official source, opens in a new tab)
- Grenfell Tower Inquiry: Government Progress Report, September 2026 (official source, opens in a new tab)