In England, Approved Document B treats a warehouse as purpose group 7(a), storage and other non-residential. Without sprinklers a single storey compartment can be up to 20,000 square metres and 18 metres high. Beyond the unsprinklered limits a sprinkler system should be provided. The Approved Document has no smoke or roof vent rule for warehouses.

Last reviewed
Reading time
14 minutes
Related service
Fire Strategy Reports
A warehouse aisle between tall racking

Which purpose group is a warehouse?

Approved Document B has no warehouse purpose group. In Approved Document B Volume 2 (opens in a new tab), the guidance for England, a warehouse falls in purpose group 7(a), storage and other non-residential. Table 0.1 describes it as a place for the storage or deposit of goods or materials other than a car park. It also covers "any building not within purpose groups 1 to 6".

Paragraph 0.20 says purpose groups represent different levels of hazard. A purpose group can apply to a whole building or to a single compartment and should relate to the main use of the building or compartment. The numbers that follow all depend on that classification.

Mixed uses need care. Under paragraph 0.21 an ancillary use is given its own purpose group where the building or compartment is more than 280 square metres and the ancillary use is more than one-fifth of the floor area. Where the purpose group is in doubt, paragraph 0.22 says "the more onerous guidance should be applied".

Our fire strategy reports service states the purpose group and the reasoning for it at the start of a warehouse strategy because the rest of the design depends on it. The industrial and warehouses sector page covers the wider approach.

Maximum compartment sizes for storage buildings

Table 8.1 sets the largest compartment for each purpose group. For storage buildings it limits single storey compartments by floor area and height and multi-storey compartments by volume. Industrial buildings are limited by floor area instead.

Approved Document B Volume 2, Table 8.1: storage and industrial compartment limits (England)
BuildingWithout sprinklersWith sprinklers throughout to Appendix E
Storage, single storey20,000 square metres floor area and 18 metres compartment heightNo limit
Storage, multi-storey20,000 cubic metres (4,000 cubic metres for storeys at least 18 metres above ground)40,000 cubic metres (8,000 cubic metres for storeys at least 18 metres above ground)
Industrial, single storeyNo limitNo limit
Industrial, multi-storey7,000 square metres (2,000 square metres above 18 metres)14,000 square metres (4,000 square metres above 18 metres)

Note 5 to the table says compartment height is measured from finished floor level to the underside of the roof or ceiling. The table recommends that where the limits for a building without sprinklers are exceeded, "a sprinkler system in accordance with Appendix E should be provided". Note 3 warns that some industrial and storage uses subject to other legislation, such as the storage of LPG and certain chemicals, may face additional limits on floor area or additional sprinkler provisions.

Paragraph 8.11 lists where compartment walls and floors should be provided in purpose groups 3 to 7, including every wall needed to meet Table 8.1. One case matters for multi-let warehouses. In shop, industrial or storage premises every wall or floor dividing a building into separate occupancies should be a compartment wall or floor, whether or not the occupiers fall in the same purpose group. Our guide to compartmentation and fire stopping explains how compartment lines are built and kept intact.

When does a warehouse need sprinklers?

Approved Document B gives two triggers for a storage building in England. The first is size. Where a compartment exceeds the Table 8.1 limits for an unsprinklered building, a sprinkler system should be provided. For a single storey building that means more than 20,000 square metres or more than 18 metres high. For a multi-storey building it means more than 20,000 cubic metres (4,000 cubic metres for storeys at least 18 metres above ground). The second is height. Paragraph 8.14 says purpose groups 3 to 7(a) "require sprinklers where there is a top storey above 30m".

A sprinkler system provided under Part B should follow Appendix E. Sprinklers should be provided throughout the building or separated part, unless acting as a compensatory feature to address a specific risk. For non-residential buildings they should meet BS EN 12845, including the relevant hazard classification and the additional reliability and availability measures in Annex F of that standard. The Approved Document says such a system "is therefore to be regarded as a life safety system".

Sprinklers also change other provisions. Paragraph E2 lists them, including raised storage areas (paragraph 7.7), compartment sizes (Table 8.1), fire resistance (Table B2), portal frames (paragraph 13.16), unprotected areas (paragraph 13.22), firefighting shaft location (paragraph 17.8) and basement smoke extract (paragraph 18.11). Paragraph E4 adds that where a design varies from the Approved Document, sprinkler protection can sometimes be used as a compensatory feature. Our guide to fire engineered solutions explains that route.

The fire service wants a lower threshold. The NFCC's policy statement on automatic water suppression systems (opens in a new tab) says government should lower the threshold for sprinklers in all storage and warehouses to 4,000 square metres, with different thresholds below that figure depending on the type of material stored. That is a fire service position and not law or guidance.

The Building Safety Regulator published research on fire safety trigger thresholds (opens in a new tab) in Approved Document B on 22nd December 2025. Its findings and recommendations "do not represent government policy". Its summary records that among non-residential buildings, storage buildings had the lowest probability of fatalities and of injury given a fire.

Insurers often want more. Paragraph 0.7 says the Building Regulations are intended to ensure a reasonable standard of life safety in a fire and that protecting property often requires additional measures. It notes that insurers usually set higher standards and that many use the RISCAuthority Design Guide for the Fire Protection of Buildings. Agree the insurer's requirements before the sprinkler decision is fixed.

Travel distances and means of escape

Table 2.1 sets travel distance limits by purpose group and hazard. For storage and other non-residential buildings at normal hazard, the limit is 25 metres where escape is in one direction only and 45 metres where it is in more than one direction. At higher hazard the limits fall to 12 metres and 25 metres. Industrial buildings share these figures.

Note 3 to Table 2.1 says that in industrial and storage buildings the appropriate distance "depends on the level of fire hazard associated with the processes and materials being used". Higher hazard includes storing significant amounts of hazardous goods. Examples in the note include compressed, liquefied or dissolved gas, liquids with a flash point below 65 degrees C (including whisky or other alcoholic liquor), corrosive substances, oxidising agents and substances liable to spontaneous combustion.

A change of tenant or stock can move a warehouse from normal to higher hazard without any building work. The fire strategy should record the hazard level it assumed so the fire risk assessment can check it later.

Where the internal layout is not known, note 1 says direct distance should be assessed instead, taken as two-thirds of the travel distance. Table 2.3 allows the 750mm minimum gangway width to be reduced to 530mm between fixed storage racking, except in public areas of shop and commercial buildings.

Paragraph 1.5 says automatic fire detection and alarm should be provided in non-residential occupancies where a fire could break out in an unoccupied part of the premises and prejudice escape from occupied parts. A storage area is one of its examples.

Mezzanines and raised storage floors

Raised storage floors are common in warehouses and they change the fire design. Paragraph 7.6 says normal fire resistance provisions "may be too onerous" for raised, free-standing floors in single storey buildings used for industrial and storage purposes. The paragraph warns that raised storage "can alter the effective number of storeys in the building".

Paragraph 7.7 accepts a raised storage structure without the Table B2 fire resistance where all of the following apply.

  • It has only one tier.
  • It is used for storage only.
  • The number of people using it is small and they are not members of the public.
  • It is open above and below.
  • Means of escape meets Sections 2 to 5.
  • It is no more than 10 metres in width or length and no more than half the floor area of the space.

With automatic detection and alarm to BS 5839-1 on the lower level, the floor can be up to 20 metres in either width or length. With sprinklers throughout to Appendix E, "no limits are set for the size of the floor". Paragraph 7.7(g) says the dimension and area may be varied if agreed with the building control body and the fire and rescue service. The safety of firefighters and the distance they may need to travel over or under the floor must be considered.

A raised floor outside these limits falls back on the normal fire resistance provisions and may add a storey to the building. That can change the compartment limits, the fire resistance and the escape design all at once.

Are smoke vents required in a warehouse roof?

Approved Document B Volume 2 contains no smoke or roof vent rule for warehouses. Its smoke venting section, Section 18, covers basements only. The only mention of roof venting in the volume is a note to paragraph 13.16 on portal frames.

Section 18 is titled "Venting of heat and smoke from basements". Each basement space should have one or more smoke outlets, with a combined clear area of at least 1/40 of the floor area of the storey served. A sprinklered basement may use mechanical extract instead.

Paragraph 13.16 deals with portal frames, which near a boundary may need protection to the rafters as well as the columns. Its note describes existing buildings designed with "some form of roof venting to give early heat release" and gives PVC rooflights covering some 10 percent of the floor area as an example.

Roof vents may still appear in a warehouse strategy. An insurer may ask for them or an engineered solution may rely on them. Neither reason comes from a rule in the Approved Document. As at 23rd November 2026, no other official guidance on roof smoke and heat venting in single storey warehouses is published on GOV.UK.

Paragraph 10.11 still applies. It says that under fire conditions ventilation and air-conditioning systems should be compatible with smoke control systems. Our guide to smoke control in buildings covers the systems the Approved Document does describe.

Structure, fire resistance and boundaries

Table B2 sets the fire resistance of elements of structure. The figures below are for storage and other non-residential buildings not described elsewhere in the table. For a single storey building the "Up to 5" metre column applies.

Approved Document B Volume 2, Table B2: fire resistance for storage buildings (England)
PositionWithout sprinklersWith sprinklers
Basement more than 10 metres deep120 minutes90 minutes
Basement up to 10 metres deep90 minutes60 minutes
Top floor up to 5 metres above ground60 minutes30 minutes (60 minutes for compartment walls separating buildings)
Top floor up to 11 metres above ground90 minutes60 minutes
Top floor up to 18 metres above ground90 minutes60 minutes
Top floor up to 30 metres above ground120 minutes90 minutes
Top floor more than 30 metres above groundNot permitted120 minutes (90 minutes for elements not forming part of the structural frame)

Boundaries matter more for storage than for most uses. Paragraph 13.17 says that when using BRE report BR 187 the radiation intensity should be taken as 168 kW per square metre for shop and commercial, industrial and storage buildings. The figure for residential, office and assembly buildings is 84 kW per square metre.

For small buildings no more than 10 metres high, Table 13.1 sets how much of each side can be unprotected area at each distance from the relevant boundary. For shop, industrial and storage buildings 1 metre allows 4 percent, 10 metres allows 40 percent and 25 metres allows 100 percent. These distances are double those for residential, office and assembly buildings. In a building sprinklered throughout, paragraph 13.22 allows either the boundary distance to be halved to a minimum of 1 metre or the unprotected area to be doubled.

Fire service access, water supplies and firefighting shafts

Under Section 15, a building up to 2,000 square metres with a top storey no more than 11 metres above ground should have pump appliance access to the less onerous of 15 percent of the perimeter or within 45 metres of every point of the footprint. Larger buildings without fire mains follow Table 15.1. Total floor area is the sum of all storeys excluding basements. For storage buildings, note 2 says height is measured to mean roof level.

Approved Document B Volume 2, Table 15.1: vehicle access to buildings not fitted with fire mains (England)
Total floor areaTop storey up to 11 metres (pump appliance)Top storey over 11 metres (high reach appliance)
Up to 2,000 square metresSee paragraph 15.115 percent of perimeter
2,000 to 8,000 square metres15 percent of perimeter50 percent of perimeter
8,000 to 16,000 square metres50 percent of perimeter50 percent of perimeter
16,000 to 24,000 square metres75 percent of perimeter75 percent of perimeter
Over 24,000 square metres100 percent of perimeter100 percent of perimeter

Paragraph 15.3 says every elevation with vehicle access should have a door at least 750mm wide, with no more than 60 metres between doors or between a door and the end of the elevation. Dead-end access routes longer than 20 metres require turning facilities.

Where vehicle access falls short of Table 15.1, paragraph 16.3 says buildings without firefighting shafts should have fire mains, with a maximum hose distance of 45 metres from the outlet to the furthest point. Paragraph 17.12 says the fire and rescue service should be able to open and close rolling shutters manually without a ladder.

Paragraph 16.8 says a building requires additional hydrants where it has a compartment of more than 280 square metres and is being erected more than 100 metres from an existing hydrant. Where there is no piped supply or the pressure and flow are not enough, paragraph 16.13 gives alternatives subject to consultation with the local fire and rescue service. They include a charged static tank of at least 45,000 litres.

Paragraph 17.2 says a building with a storey more than 18 metres above fire service vehicle access level should have one or more firefighting shafts containing a firefighting lift. Paragraph 17.5 calls for at least two shafts where such a storey is 900 square metres or more.

Paragraph 17.6 provides for at least two firefighting shafts where a storey of 900 square metres or more is 7.5 metres or more above access level. It names only the shop and commercial, assembly and recreation and industrial purpose groups. Storage is not among them, although paragraphs 17.2 and 17.5 still apply at 18 metres.

Planning, occupation, Wales and Scotland

There is no national planning fire statement for warehouses in England. The Gateway 1 fire statement applies only to relevant buildings of 18 metres or 7 storeys that contain two or more dwellings or educational accommodation, as our Gateway 1 fire statement guide explains. In London, Policy D12(B) of the London Plan 2021 (opens in a new tab) says all major development proposals should be submitted with a Fire Statement. For non-residential uses, major development is generally floor space of 1,000 square metres or more or a site of 1 hectare or more.

Once the warehouse is in use, the Regulatory Reform (Fire Safety) Order 2005 (opens in a new tab) applies in England and Wales. Article 9(1) says the responsible person "must make a suitable and sufficient assessment of the risks to which relevant persons are exposed". Section 19 of Approved Document B Volume 2 covers the fire safety information handed over under Regulation 38, which our Regulation 38 guide explains.

Wales has its own Approved Document B (opens in a new tab). Table 12 of its Volume 2 gives the same storage compartment figures as the English Table 8.1. Planning authorities in Wales must consult the fire and rescue authority on applications validated on or after 25th April 2022 for listed types of development, including buildings creating 1,000 square metres or more of floor space and sites of 1 hectare or more.

Scotland sets smaller single storey compartments. Under the non-domestic Technical Handbook (opens in a new tab) (April 2026), a Class 1 storage building contains hazardous goods or materials and has a maximum single storey compartment area of 1,000 square metres. Any other storage building is Class 2, with a maximum of 14,000 square metres. Both need Long fire resistance and the areas may be doubled where there is an automatic fire suppression system.

Our fire strategy reports service produces warehouse strategies for building control, the fire service and the insurer in England, Wales and Scotland. Our guide to data centre fire safety covers a related building type.

Sources

This guide was written from these official sources. Check the current version before relying on any figure.

Common questions

More on this topic.

All fire strategy questions

In England, Approved Document B says a sprinkler system should be provided where a storage compartment exceeds the Table 8.1 limits for an unsprinklered building, such as 20,000 square metres or 18 metres high for a single storey. Purpose group 7(a) buildings also require sprinklers where there is a top storey above 30 metres. Wales uses the same compartment figures and Scotland sets its own.

Keep reading

Related guides.

Talk to an engineer

Tell us about the building

Send us the drawings, the building type and the stage you are at. We reply the same day with a clear scope, programme and fixed fee.