What is an evacuation strategy?
An evacuation strategy decides who leaves a building in a fire, in what order and with what help. It is one of the first decisions in a fire strategy because stair widths, alarm type, compartmentation and smoke control all follow from it. Our fire strategy reports set it out with the assumptions behind it.
Approved Document B (opens in a new tab) ties the alarm to the strategy. Volume 2 paragraph 1.13 says that where the strategy is simultaneous evacuation, actuation of the fire alarm should give warning from all sounders. Where phased evacuation is planned, a staged alarm system is appropriate.
The fire safety information handed over under Regulation 38 should record the escape strategy, for example simultaneous or phased. The Gateway 1 planning fire statement form in England asks for it from a list of simultaneous, phased, staged, stay put, progressive horizontal and delayed.
Whichever strategy is chosen, the building has to be capable of being run to it. Paragraph 0.6 of Approved Document B says any reliance on an unrealistic or unsustainable management regime cannot be considered to have met the requirements of the regulations.
How stay put works in blocks of flats
Stay put is the basis of flat design in Approved Document B Volume 1 (opens in a new tab). Paragraph 3.3 says provisions are recommended to support a stay put evacuation strategy for blocks of flats. It is based on the principle that a fire is contained in the flat of origin and common escape routes are maintained relatively free from smoke and heat. Occupants of other flats can then remain.
Paragraph 3.2 lists the assumptions behind it. Any fire is likely to be in a flat, there is no reliance on external rescue and simultaneous evacuation of all flats is unlikely to be necessary because of compartmentation. Fires in the common parts should not spread beyond the fabric in the immediate vicinity.
Stay put does not mean residents cannot leave. Paragraph 3.3 says the common means of escape needs enough protection to let occupants escape if they choose to or are instructed or aided to by the fire service. Common escape routes in flats therefore need a higher standard of protection than in other buildings so they remain available for longer.
The NFCC Simultaneous Evacuation Guidance (opens in a new tab) says stay put relies on the fire separation between flats and between each flat and the common parts, through fire-resisting doors, walls, floors and ceilings. The external walls should also adequately resist the spread of fire.
The 2026 amendments to Volume 1 say it is probable that some smoke will get into the common corridor or lobby from a fire in a flat. There should therefore be some means of ventilating them to control smoke and protect the common stairs, which our smoke control guide covers.
The NFCC's stay put advice (opens in a new tab) tells residents that if a fire is in the building but not in their home, they are usually safer to stay in their flat unless heat or smoke is affecting them. They should still call 999 immediately and the advice can change depending on the circumstances.
Simultaneous evacuation
In simultaneous evacuation everyone leaves when the alarm sounds. Approved Document B Volume 2 (opens in a new tab) paragraph 3.16 says the width of escape stairs should take account of the number of people using them while evacuating all storeys at the same time. It says these stairs should be designed to allow simultaneous evacuation.
- All stairs serving basements
- All stairs serving buildings with open spatial planning
- All stairs serving residential (other) buildings in purpose group 2(b) or assembly and recreation buildings in purpose group 5
Table 3.2 of Volume 2 gives the stair capacities for simultaneous evacuation. In student flats, Volume 1 paragraph 1.11 says that where a total evacuation strategy is adopted, the alarm system should follow the Volume 2 guidance for buildings other than dwellings.
The Residential PEEPs regulations define it as a strategy where the responsible person has determined that all persons in the building should leave immediately in the event of a fire. GOV.UK guidance says that in a residential building this is typically an interim change from stay put due to ongoing remediation, though it can be a permanent or temporary strategy as decided by the fire risk assessment.
Volume 2 paragraph 2.34 says care homes for the elderly should generally be designed for progressive horizontal evacuation. For other care homes the most appropriate of progressive horizontal or simultaneous evacuation should be identified. Our guide to progressive horizontal evacuation covers that strategy.
Phased evacuation in tall buildings
Volume 2 paragraph 3.19 says that in a phased evacuation the first to be evacuated are those with reduced mobility and those on the storey most immediately affected by the fire. If needed, later evacuation is done two floors at a time. Phased evacuation cannot be used in every type of building but can be advantageous for escape stairs in high buildings.
The benefit is stair width. Paragraph 3.19 says phased evacuation enables stairs to be narrower than with simultaneous evacuation and may be used for any building not identified in paragraph 3.16. Table 3.3 sets stair widths against the maximum number of people in any storey and assumes a phased evacuation of the fire floor first, followed by evacuation of not more than two floors at a time.
Paragraph 3.21 lists the design conditions the building has to meet.
- Stairs approached through a protected lobby or protected corridor at each storey except the top storey
- Lifts approached through a protected lobby
- Every floor a compartment floor
- Automatic sprinklers throughout where there is a storey over 30m, in line with Appendix E
- A fire warning system to at least L3 of BS 5839-1
- An internal speech communication system between a control point at fire and rescue service access level and a fire warden on every storey, with any voice alarm to BS 5839-8
Paragraph 3.20 says phased evacuation in buildings with a storey over 30m introduces the potential for escaping people to impede firefighters, which can be addressed by consulting the fire and rescue service about special management procedures. In very tall buildings, typically with a storey over 45m, physical measures such as discounting a stair may need to be incorporated.
A common error is proposing phased evacuation for basements, open spatial planning or purpose groups 2(b) and 5, which paragraphs 3.16 and 3.19 exclude. Our smoke control and evacuation modelling service tests phased strategies where the design needs more than the tables.
Temporary simultaneous evacuation and the NFCC guidance
The NFCC Simultaneous Evacuation Guidance, fourth edition, issued on 18th August 2022, is written for existing blocks of flats that can no longer support stay put. The NFCC page (opens in a new tab) still shows the fourth edition as at 23rd November 2026.
Its scope is narrow. It is primarily designed for buildings that pose a significant and immediate risk to residents, cannot support stay put and where short term interim measures are the only alternative to immediate prohibition by the enforcing authority. It is non-statutory guidance.
The decision sits with the Responsible Person. The guidance says a Responsible Person, with advice from a Competent Person where necessary, may determine that all or parts of the building can no longer support stay put. Fire risk assessments should determine whether the safety measures support the current strategy and recommend a change where necessary. Responsible Persons should notify the local fire and rescue service of any change because it will need to consider its operational response.
The guidance says a change will need some means of detecting a fire and warning residents to evacuate. It treats a waking watch and a common fire alarm system as ways of doing both. Table 4.2 sets these timeframes.
| Stage | Timeframe |
|---|---|
| Immediate measures | Immediately |
| Transition plan where a waking watch is used | Within a month |
| Transition period, for example to a common fire alarm | No longer than 6 months |
| Short term, to formulate a remediation plan | No longer than 12 months |
| Longer term | 12 months or more |
The NFCC says the guidance seeks to actively discourage the ongoing and prolonged use of a waking watch. Interim measures are not a substitute for remediation and Responsible Persons must proactively engage with residents when they change the strategy.
Evacuation alert systems in new blocks of flats
An evacuation alert system lets the fire and rescue service sound alerts in the flats on a single floor, several floors or the whole building, as the Scottish Technical Handbook describes it. In England, Volume 1 paragraph 15.17 says that in blocks of flats with a top storey over 18m above ground level an evacuation alert system should be provided in accordance with BS 8629. The provision came in with the 2022 amendments (opens in a new tab), which took effect on 1st December 2022 with a six month start window for work under earlier notices or plans.
| Nation | Where | Guidance | Date |
|---|---|---|---|
| England | Blocks of flats with a top storey over 18m above ground level | Approved Document B Volume 1 paragraph 15.17, to BS 8629 | 1st December 2022 |
| Wales | Blocks of flats with a top storey over 18m above ground level | Welsh Approved Document B Volume 2 paragraph 18.20, to BS 8629 | 20th December 2025 |
| Scotland | Domestic buildings with a storey more than 18m above ground level | Domestic Technical Handbook clause 2.14.8, to BS 8629:2019 | In the April 2026 handbook (start date not stated there) |
An evacuation alert system is not a fire alarm. The NFCC guidance says BS 8629 systems on their own would be unsuitable as a mitigation measure because they cannot detect fire. The Scottish handbook adds that the system should not be a compensatory measure or a component of a fire engineering solution.
The national evacuation guidelines for fire and rescue services (opens in a new tab) were published on 5th February 2024 in response to Grenfell Tower Inquiry Phase 1 recommendation 33.22a. Guideline 3 says that where an evacuation alert system is present, using it to initiate evacuation can significantly reduce total evacuation time compared with relying on door-knocking alone.
Residential PEEPs and the government's position
Personal emergency evacuation plans for residents of blocks of flats took years to settle in England. The Home Office consulted on PEEPs from 8th June to 19th July 2021. Its response of 18th May 2022 said the government was currently unable to mandate PEEPs in high-rise residential buildings because of issues of practicality, proportionality and safety.
The EEIS+ consultation (opens in a new tab) followed in 2022 and its response of 2nd December 2024 introduced proposals called Residential PEEPs. The Fire Safety (Residential Evacuation Plans) (England) Regulations 2025 were made on 3rd July 2025 and came into force on 6th April 2026.
SI 2025/797 (opens in a new tab) applies to a specified residential building. Regulation 3 defines this as a building which contains two or more sets of domestic premises and which is at least 18 metres in height above ground level, has at least seven storeys or is more than 11 metres in height above ground level and has a simultaneous evacuation strategy. Height is measured to the top storey in accordance with Appendix D to Approved Document B and storeys below ground level are ignored. The regulations apply in England only and do not apply to military premises or domestic premises within the Palace of Westminster.
The duties fall on the responsible person and are listed here in the order of the regulations.
- Use reasonable endeavours to identify relevant residents (regulation 5)
- Offer to carry out a person-centred fire risk assessment and carry one out on request (regulation 6)
- Implement reasonable and proportionate mitigating measures (regulation 7)
- Agree and record an emergency evacuation statement (regulation 8)
- Review at least every 12 months (regulation 9)
- With the resident's explicit consent, give the local fire and rescue authority the flat number, floor number, basic information on the help needed and whether there is a statement (regulation 10)
- Prepare a building emergency evacuation plan, give a copy to the fire and rescue authority, place a copy in any secure information box and review it within 12 months and every 12 months after (regulation 13)
The building emergency evacuation plan must include the instructions to residents on the evacuation strategy already required by regulation 9 of the Fire Safety (England) Regulations 2022 (opens in a new tab). Since 23rd January 2023 that regulation has required those instructions to be displayed in buildings with two or more sets of domestic premises and common parts used for evacuation, with a copy to new residents and to all residents every 12 months.
The GOV.UK Residential PEEPs page (opens in a new tab), last updated on 6th April 2026, links to guidance for responsible persons on these duties. A strategy stated clearly in the fire strategy report is far easier to carry into these documents once the building is occupied.
Evacuation lifts and second staircases
Volume 2 paragraph 5.32 says lifts should generally not be used in a fire unless their use forms part of a management plan for evacuating people and the lifts are appropriately sited and protected and contain safety features to ensure they remain usable during a fire. It points to Annex G to BS 9999 for evacuation lift design.
The 2026 amendments (opens in a new tab), in effect from 30th September 2026, add building design provisions for evacuation lifts in blocks of flats. Paragraph 3.29 says that where evacuation lifts are provided, they should be located within an evacuation shaft containing a protected stairway, evacuation lift and evacuation lift lobby. The lobby should provide a refuge area, have direct access to a protected stairway and not be directly accessible from any flat. This applies where evacuation lifts are provided and does not itself call for them.
The same amendments recommend more than one common stair where a block of flats has a top storey of 18m or more in height, with an 18 month transition for work under earlier notices or plans. The FRS evacuation guidelines report that in a two-staircase building, using one stair for firefighters and the other solely for evacuation decreased evacuation time in live tests by up to 53 percent. Our guide to second staircases over 18 metres covers the rule and its transition.
As a proposal only, the Building Safety Regulator's consultation on a review of Approved Document B, published with MHCLG, proposed a minimum of two stairs and two evacuation lifts in all new residential buildings above 18m. It noted that historically the guidance relied instead on a stay-put strategy and intervention from the fire and rescue service. The consultation ran from 25th March 2026 to 11:59pm on 1st July 2026 and as at 23rd November 2026 GOV.UK says the feedback is being analysed. Our guide to London Plan Policy D5(B5) covers evacuation lifts in London planning.
Wales and Scotland
Wales has its own Approved Document B. The Welsh Volume 2 (opens in a new tab) rests on the same assumption for flats, saying compartmentation gives a low probability of fire spread beyond the flat of origin so that simultaneous evacuation of the building is unlikely to be necessary. Its evacuation alert system provision (opens in a new tab) at paragraph 18.20 took effect on 20th December 2025 with a six month start window.
The Residential PEEPs regulations and regulation 9 of the Fire Safety (England) Regulations 2022 both apply in England only. See our Wales page for projects there.
Scotland uses the Technical Handbooks. Clause 2.9.24 of the Domestic Technical Handbook (opens in a new tab) says occupants should be able to remain safely inside the building until the fire has burnt itself out or has been contained and it is safe to use the escape route. Clause 2.14.8 covers evacuation alert systems, as set out above. See our Scotland page for projects there.
In every nation the evacuation strategy is a design decision that the people running the building have to live with. Our fire strategy reports set out the strategy, the features it depends on and the management it assumes.
Sources
This guide was written from these official sources. Check the current version before relying on any figure.
- Approved Document B Volume 1: Dwellings (England) (official source, opens in a new tab)
- Approved Document B Volume 2: Buildings other than dwellings (England) (official source, opens in a new tab)
- Approved Document B amendment booklet, June 2022 (official source, opens in a new tab)
- 2026 amendments to Approved Document B (official source, opens in a new tab)
- NFCC Simultaneous Evacuation Guidance, fourth edition (official source, opens in a new tab)
- Fire Safety (Residential Evacuation Plans) (England) Regulations 2025 (official source, opens in a new tab)
- Fire Safety (England) Regulations 2022, regulation 9 (official source, opens in a new tab)
- Residential PEEPs: guidance for responsible persons (official source, opens in a new tab)
- Emergency evacuation information sharing (EEIS+) consultation (official source, opens in a new tab)
- Personal emergency evacuation plans consultation (official source, opens in a new tab)
- Evacuation guidelines for fire and rescue services (official source, opens in a new tab)
- Review of Approved Document B: fire safety guidance (consultation) (official source, opens in a new tab)
- Amendments to Approved Document B, Wales, effective 20th December 2025 (official source, opens in a new tab)
- Building Standards Technical Handbook, domestic, April 2026 (Scottish Government) (official source, opens in a new tab)