Why common corridors and stairs are ventilated
In a block of flats with a stay put strategy, the common stair is the escape route for anyone who leaves and the route in for firefighters. Approved Document B (opens in a new tab) Volume 1 paragraph 3.53 says it is probable that some smoke will get into the common corridor or lobby from a fire in a flat. There should therefore be some means of ventilating the common corridors and lobbies to control smoke and protect the common stairs. This adds to the protection given by the fire doors to the stair and gives some protection to the corridors and lobbies themselves.
The underlying requirements are B1 (means of escape) and B5 (facilities for firefighters). Ventilation can be natural (paragraphs 3.54 to 3.57) or mechanical (paragraph 3.58).
The 2026 amendments (opens in a new tab), which took effect on 30th September 2026, added text on evacuation lifts. Where evacuation lifts are provided, their shafts should have the same minimum protection as the stair. Any smoke control system designed to protect the stair should extend the same protection to the evacuation lift and its lobby. Our guide to evacuation strategies explains stay put and the alternatives.
The same amendments renumbered this part of Section 3. Old paragraphs 3.49 to 3.54 are now 3.53 to 3.58. Projects still working under the earlier guidance may cite the old numbers. Our smoke control and evacuation modelling service designs these systems and the engineered cases behind them.
Natural ventilation with automatic opening vents
Except in buildings that comply with Diagram 3.9, paragraph 3.54 says the corridor or lobby directly in front of each storey exit should have a smoke vent. It should be located as high as practicable, with its top edge at least as high as the top of the door to the stair. Diagrams 3.7 and 3.8 shade the zones where an external wall vent or smoke shaft may be located.
- A smoke vent on an external wall should have a minimum free area of 1.5m² (paragraph 3.55a).
- A vent to the outside with a minimum free area of 1m² should be provided from the top storey of the stair (paragraph 3.56).
- In single stair buildings the smoke vents on the fire storey and the vent at the head of the stair should be activated by smoke detectors in the common parts (paragraph 3.57).
- In buildings with more than one stair the smoke vents may be activated manually.
- The control system should open the vent at the head of the stair before or at the same time as the vent on the storey where the fire is located.
A vent that opens automatically on smoke detection is what most people call an AOV, an automatic opening vent. Approved Document B uses that term for the vent at the top of the stair in Diagram 3.9. Paragraph 1.10 notes that detectors in the common parts of a block may need to operate smoke control or other fire protection systems but do not usually sound an audible warning.
Free area is the figure that matters, not the size of the frame. Appendix D paragraph D5 and Diagram D7 explain how it is measured.
Natural smoke shafts
The second natural option is for the corridor or lobby vents to discharge into a vertical smoke shaft, closed at the base. Paragraph 3.55b sets its criteria.
- A minimum cross-section of 1.5m², with a minimum dimension of 0.85m.
- Open at roof level at least 0.5m above any surrounding structures within 2m horizontally.
- Extending at least 2.5m above the ceiling of the highest storey served.
- Vents of at least 1m² free area from the corridor or lobby into the shaft, at the head of the shaft and at all internal locations such as safety grilles.
- Constructed of class A1 materials.
- Vents that are Sa rated fire doorsets or smoke control dampers.
- Vertical, with a maximum of 4m at a maximum inclined angle of 30 degrees.
The operating sequence matters as much as the sizes. If smoke is detected in the common corridor or lobby, the vents on the storey where the fire is located, at the top of the shaft and to the stair should open together. Vents from the corridors or lobbies on all other storeys should remain closed, even if smoke is later detected on those storeys. Opening vents on other floors would let the shaft spread smoke instead of removing it.
A protected shaft containing a stair should not contain a ventilating duct, except one for pressurising or only ventilating the stair (paragraph 7.26). Paragraph 9.11 adds that ventilation and air-conditioning systems should be compatible with smoke control systems under fire conditions. Our guide to compartmentation and fire stopping covers protected shafts.
Small single stair buildings
Diagram 3.9 and paragraph 3.32 cover small single stair buildings, with a top storey a maximum of 11 metres above ground and no more than three storeys above the ground storey. Instead of corridor vents they can have a high-level openable vent of at least 1m² free area at each storey. Alternatively a single 1m² vent at the head of the stair can be used, operable remotely at the fire and rescue service access level.
Where there are no more than two flats per storey and the flats have protected entrance halls, the lobby between the common stair and the flat entrance is not essential. Where that lobby is left out, an automatic opening vent with a geometric free area of at least 1m² is required at the top of the stair, operated on detection of smoke at any storey in the stair. In the other small single stair layout, Diagram 3.9 limits travel across the lobby to 4.5 metres. This rises to 7.5 metres if smoke control is provided in the lobby.
Because the stair protection in these buildings can depend on the flats' entrance halls, changing a flat layout can affect the common stair. Our guide to open plan flats covers that link.
Mechanical ventilation and pressurisation
Paragraph 3.58 deals with mechanical systems in one sentence. It says guidance on the design of smoke control systems that use pressure differentials is available in BS EN 12101-6. For the common parts of flats Approved Document B gives no design figures such as pressures, air velocities or extract rates. The design basis has to come from the standard and from the engineering case for the building.
Volume 2 uses pressurisation as an alternative in several places for buildings other than dwellings.
- Dead-end corridors over 4.5m should be separated by self-closing fire doorsets. Alternatively the stairs and corridors may be protected by a pressurisation system complying with BS EN 12101-6 (paragraph 2.28).
- Stairs need not be discounted in turn when they are protected by a smoke control system designed to BS EN 12101-6 (paragraphs 3.14 and 3.15).
- Protected lobbies or corridors should be provided for a single stair serving more than one storey above or below ground, a stair serving a storey at 18m or more, a building designed for phased evacuation and a firefighting stair. For the first three a smoke control system as described in paragraph 3.15a may be used instead (paragraph 3.34).
- Unless pressurisation complying with BS EN 12101-6 is used, doors marked S in Table C1 should meet a stated leakage limit or the Sa classification (Table C1 note 2).
In blocks of flats, firefighting shafts should be provided where a storey is more than 18 metres above fire service vehicle access level (paragraph 15.2). Their stair and lobby should have a means of venting smoke and heat, with Approved Document B pointing to clause 27.1 of BS 9999. Where the shaft only serves flats, the note to Diagram 15.1 allows the provisions from paragraph 3.53 to be followed instead.
The London Fire Brigade's Q1 2020 fire engineering thematic report (opens in a new tab) audited 15 developments with 36 cores, where residential smoke control was specifically targeted. In 20 percent of cores the solution failed the check on whether it worked and in 55 percent it failed the check on whether it was in the fire risk assessment. These are 2020 figures from a series that has since stopped. Our guide to fire engineered solutions covers how such a case is built and agreed.
Atria and basements
Appendix A defines an atrium as a continuous space that passes through one or more structural floors within a building, not necessarily vertically. Volume 2 paragraph 0.16 says a building with an atrium passing through compartment floors may need special fire safety measures and points to Annexes B and C of BS 9999. For Approved Document B, BS 9999 applies only where the atrium breaches a compartment (paragraph 8.13). In practice an atrium is often where smoke control becomes an engineered design.
Basements have their own section in both volumes, Section 18 of Volume 2 and Section 16 of Volume 1. The main provisions are these.
- Each basement space should have one or more smoke outlets.
- Every basement storey should have outlets to open air, except one of a maximum 200m² with its floor a maximum of 3m below ground.
- Natural outlets should be at high level and evenly distributed, with a combined area of at least 1/40 of the floor area of the storey they serve.
- Where the basement is sprinklered, mechanical extract may replace natural venting. It should give at least 10 air changes per hour and handle gas temperatures of 300°C for not less than one hour.
- Mechanical extract should be activated by the sprinklers or by an automatic detection system to BS 5839-1, minimum L3.
Car parks follow their own provisions in Section 11 of Volume 2. Our guide to car park ventilation and smoke clearance covers them.
Maintenance and testing duties
Once a building is occupied, article 17 of the Fire Safety Order (opens in a new tab) applies in England and Wales. The responsible person must ensure that facilities, equipment and devices provided under the Order or any other enactment are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair. Article 38 (opens in a new tab) applies the same duty to facilities for the use or protection of firefighters.
Article 17 does not fix a servicing interval. It asks for a suitable system of maintenance, which in practice is informed by the design, the manufacturer's recommendations and the fire risk assessment.
In England the Fire Safety (England) Regulations 2022 (opens in a new tab) add monthly checks in high-rise residential buildings. The regulations define these as buildings with two or more sets of domestic premises that are at least 18 metres above ground level or have at least seven storeys. They came into force on 23rd January 2023 and apply in England only. Smoke control systems are key fire-fighting equipment under regulation 6(7) and detectors linked to smoke control count as essential fire-fighting equipment in the common parts.
| Duty | What it involves |
|---|---|
| Monthly routine checks | Check lifts for use by firefighters, evacuation lifts and essential fire-fighting equipment, which includes smoke control systems |
| What a routine check is | A check that the equipment is in efficient working order and good repair, carried out in accordance with the relevant industry standard or the manufacturer's recommendations in an operators' manual |
| The smoke control check | Typically one test a month that the system responds to a signal from the associated fire detection and alarm system. It should also respond to any manual control for the fire and rescue service |
| Faults | Take steps to rectify the fault. If it cannot be rectified within 24 hours of being identified, report it to the local fire and rescue authority by electronic means as soon as reasonably practicable and report again when it is rectified |
| Records | Record the monthly checks and make the record accessible to residents, for example on a notice board or through a residents' association |
The check guidance (opens in a new tab) says these checks generally involve only visual inspection or simple functional operating checks and are not expected to need specialists. They are in addition to the servicing and maintenance of the systems, usually by a contractor, that the Fire Safety Order requires. After a fault, responsible persons should consider its impact on means of escape, any mitigation needed and whether to review the fire risk assessment.
The regulation 7 fact sheet (opens in a new tab) says responsible persons should consider signs on or by defective equipment, whatever the expected repair time. Under regulation 6 the floor plans for high-rise residential buildings identify smoke control systems and the building plan shows the location of their central controls.
For existing blocks, the 2011 Local Government Association guide Fire safety in purpose-built blocks of flats (opens in a new tab) gives good practice, not law. It suggests AOVs should be tested once a month using the manual controls, with their detectors and controls tested at least once a year. It adds that those servicing extract and pressurisation systems should be familiar with the fire engineering performance parameters used in the design. The guide's cover note says it should be viewed as no longer comprehensive.
Design information and handover
The smoke control design has to survive handover. Under Regulation 38, Section 17 of Volume 1 asks the fire safety information to show any smoke control systems or ventilation systems with a smoke control function, including the mode of operation and control systems. For complex buildings it asks for the smoke control system design, including any air inlets, smoke outlets, mode of operation and control systems. It also asks for an outline cause and effect matrix or strategy for the building.
A system the responsible person cannot describe is hard to check each month. The cause and effect matrix is what lets a monthly check confirm that the right vents open in the right order. Our guide to Regulation 38 covers the full handover duty.
Wales and Scotland
The design guidance in all three nations uses similar natural vent sizes. The duties in occupied buildings differ more.
| Nation | Design guidance | Occupied building duties |
|---|---|---|
| England | Approved Document B Volume 1 paragraphs 3.53 to 3.58, with BS EN 12101-6 for pressure differential systems | Fire Safety Order article 17 and, in high-rise residential buildings, monthly checks and fault reporting under the Fire Safety (England) Regulations 2022 |
| Wales | Welsh Approved Document B Volume 2 paragraphs 3.25 to 3.27: corridor or lobby vents of at least 1.5m² on an external wall or discharging into a shaft of at least 1.5m² (0.85m minimum dimension), a stair head vent of at least 1.0m² and mechanical ventilation pointing to BS EN 12101-6:2005 | Fire Safety Order article 17. The monthly check and reporting duties in the 2022 regulations apply in England only |
| Scotland | Domestic Technical Handbook, April 2026, clauses 2.9.14 to 2.9.16: smoke ventilation in protected lobbies, fire-fighting lobbies and protected corridors in the circumstances set out in Table 2.4 | Fire (Scotland) Act 2005, not the Fire Safety Order |
The Welsh Approved Document B (opens in a new tab) places these provisions in Volume 2 under different paragraph numbers from England. See our Wales page for projects there.
In Scotland, natural vents on an external wall of a protected lobby should be at least 1.5m² and open automatically on smoke detection, with smoke shafts as the alternative. Mechanical options are depressurisation, pressurisation or heating and ventilation systems. The domestic Technical Handbook (opens in a new tab) says more detailed guidance can be found in the BS EN 12101 series. See our Scotland page for projects there.
In every nation a smoke control system is only as good as its design, its handover information and the testing it gets in use. Our smoke control and evacuation modelling service designs the system, prepares any engineered case and writes the cause and effect narrative that commissioning is tested against.
Sources
This guide was written from these official sources. Check the current version before relying on any figure.
- Approved Document B: fire safety, GOV.UK (official source, opens in a new tab)
- Approved Document B Volume 1: Dwellings (official source, opens in a new tab)
- Approved Document B Volume 2: Buildings other than dwellings (official source, opens in a new tab)
- Approved Document B: 2026 amendments (official source, opens in a new tab)
- Regulatory Reform (Fire Safety) Order 2005, article 17 (official source, opens in a new tab)
- Regulatory Reform (Fire Safety) Order 2005, article 38 (official source, opens in a new tab)
- Fire Safety (England) Regulations 2022, regulation 7 (official source, opens in a new tab)
- Fact sheet: lifts and essential fire-fighting equipment (regulation 7) (official source, opens in a new tab)
- Check your fire safety responsibilities under the Fire Safety (England) Regulations 2022 (official source, opens in a new tab)
- Fire Safety in Purpose-Built Blocks of Flats, Local Government Association (official source, opens in a new tab)
- Approved Document B Volume 2, Wales (official source, opens in a new tab)
- Building Standards Technical Handbook, domestic, April 2026 (official source, opens in a new tab)