Why car parks have their own rules
Car parks are a special case in Approved Document B (opens in a new tab), the guidance on meeting the fire safety requirements of the Building Regulations 2010 in England. Volume 2 Section 11 gives two reasons. The fire load in a car park is well defined. The probability of fire spreading from one storey to another in a well ventilated car park is also low.
Guidance is therefore given for three ventilation scenarios, which are open-sided car parks, naturally ventilated car parks and mechanically ventilated car parks. Section 11 sits within the guidance on requirement B3, internal fire spread of the structure. It applies to purpose group 7(b), car parks designed to admit and accommodate only cars, motorcycles and passenger or light goods vehicles weighing no more than 2,500 kilograms gross.
Table 8.1 sets no limit on floor area, height or compartment volume for a car park for light vehicles. The ventilation category decides the fire resistance and much of the fire strategy. It should be settled at concept stage. Our smoke control and evacuation modelling service covers car park smoke ventilation for new and altered buildings.
When is a car park open-sided?
Open-sided is a defined status in paragraph 11.2. It matters because it brings lower fire resistance periods. For assessing fire resistance, a building, compartment or separated part containing a car park may be regarded as open-sided when all of the following apply.
- There are no basement storeys.
- Each storey is naturally ventilated by permanent openings at each car parking level.
- The aggregate vent area is at least 1/20 of that level's floor area. At least half of it is provided equally by two opposite walls, which is 1/80 on each side.
- Supporting elements at least match the fire resistance of the elements they support, including where the car park forms part of a mixed use building.
- All materials used in the construction are class A1. The listed exceptions are floor or roof surface finishes meeting B2 and B4, fire doorsets, an attendant's kiosk of no more than 15 square metres and any shop mobility facility.
The first and last tests are the easiest to miss. A car park with a basement storey cannot be open-sided, whatever the size of its openings above ground. The openings are also assessed level by level. A storey that meets the overall ratio with all its openings on one face fails. Half the area has to be split equally between two opposite walls.
Natural ventilation for car parks that are not open-sided
A car park that is not open-sided takes its fire resistance from Table B2 in Appendix B. Paragraph 11.3 says its ventilation should be either natural or mechanical. It also points to Approved Document F (opens in a new tab) for additional guidance on the ventilation of car parks.
Under paragraph 11.4 each storey should be ventilated by permanent openings at each car parking level. The aggregate free vent area should be at least 1/40 of that level's floor area. At least half of it should be provided equally by two opposite walls, which is 1/160 on each side. The openings can be at ceiling level.
That is half the opening area an open-sided car park needs. It avoids mechanical extract but does not bring the open-sided fire resistance periods. Where the minimum standard of natural ventilation is not possible, paragraph 11.5 calls for mechanical ventilation.
Mechanical smoke ventilation: 10 air changes in two parts
Paragraph 11.5 says that if the minimum standard of natural ventilation is not possible, a system of mechanical ventilation should be provided that complies with all of the following.
- Independent of any other ventilating system, other than a system that provides day to day ventilation to the car park.
- Designed to operate at 10 air changes per hour during a fire.
- Run in two parts, each capable of extracting 50 percent of the rates and able to operate alone or with the other part.
- Each part provided with an independent power supply capable of operating if the main supply fails.
- Outlets split with 50 percent at high level and 50 percent at low level.
- Ductwork classed E, I and S in accordance with BS EN 1366-8.
For further information on equipment for removing hot smoke, the guidance refers to BS EN 12101-3. It names BS 7346-7 as an alternative method of providing smoke ventilation from enclosed car parks. Paragraph 10.10 adds that car parks should have separate and independent extraction systems and that extracted air should not be recirculated.
The two part arrangement is about reliability. With each half separately powered, one failure halves the extract rather than removing it. Some car parks use a bespoke smoke control strategy instead. The government's guidance on electric vehicles notes that one can be designed to maintain a clear smoke layer height for a defined maximum fire size. Our guide to fire engineered solutions explains how such a case is built and agreed.
Day to day ventilation under Approved Document F
Approved Document F deals with ventilation for air quality, not fire. Volume 2 paragraph 1.38 says the ventilation of below ground, enclosed and multi-storey car parks should limit carbon monoxide to an average of 30 parts per million over an eight hour period. Peaks should be no more than 90 parts per million over a 15 minute period. Its note says guidance on the ventilation of car parks to manage the risk of fire is given in Approved Document B.
Paragraph 1.39 gives alternatives to those limits that may be considered to provide adequate ventilation.
- Natural openings of at least 1/20 of the floor area at each level, with at least 25 percent of that area on each of two opposing walls.
- Permanent openings of 1/40 of the floor area combined with mechanical ventilation of at least three air changes per hour.
- In a basement car park, mechanical ventilation of at least six air changes per hour.
- With either mechanical option, at least ten air changes per hour at exits and ramps where cars queue inside.
Three or six air changes for air quality is not a smoke clearance system. Paragraph 11.5 of Approved Document B does not ask the smoke system to be independent of the car park's day to day ventilation. A combined system should still meet every part of the fire specification. Volume 2 of Approved Document F is the 2021 edition and took effect in England on 15th June 2022.
Fire resistance of car park structures
Table B2 in Volume 2 sets the minimum periods. The above ground bands refer to the height of the top floor above ground in the building or separated part. For an open-sided car park the 15 minute periods are increased to 30 minutes for elements that protect the means of escape.
| Car park | Storey and band | Minimum period |
|---|---|---|
| Open-sided | Basement storeys | Not applicable |
| Open-sided | Ground or upper storeys, top floor up to 30 metres | 15 minutes |
| Open-sided | Ground or upper storeys, top floor more than 30 metres | 60 minutes |
| Any other car park | Basement, lowest basement more than 10 metres deep | 90 minutes |
| Any other car park | Basement, lowest basement up to 10 metres deep | 60 minutes |
| Any other car park | Ground or upper storeys, top floor up to 5 metres | 30 minutes |
| Any other car park | Ground or upper storeys, top floor up to 11 metres | 60 minutes |
| Any other car park | Ground or upper storeys, top floor up to 18 metres | 60 minutes |
| Any other car park | Ground or upper storeys, top floor up to 30 metres | 90 minutes |
| Any other car park | Ground or upper storeys, top floor more than 30 metres | 120 minutes |
Note 8 to the table applies to the open-sided 15 minute periods above 5 metres. It says certain steel elements under full design load are deemed to satisfy 15 minutes when tested to the European test method. These are beams supporting concrete floors with Hp/A of no more than 230 per metre, free-standing columns of no more than 180 per metre and wind bracing and struts of no more than 210 per metre.
These are the current periods. A proposal to raise them for open-sided car parks is described further down this page.
Basement car parks, stairs and lifts
Paragraph 18.15 says the Section 11 provisions for ventilation of basement car parks satisfy the requirements for venting smoke from any basement used as a car park. It therefore takes the natural or mechanical route and the basement periods in Table B2.
Other basements follow Section 18. Natural smoke outlets should total at least 1/40 of the floor area of the storey they serve. Where basement storeys have sprinklers, mechanical extract may replace natural venting. It should give at least 10 air changes per hour and handle gas temperatures of 300°C for at least one hour. Paragraph 18.11 adds that car parks are not normally expected to be fitted with sprinklers.
Paragraph 17.3 calls for firefighting shafts where a basement is more than 10 metres below the fire and rescue service vehicle access level. It also calls for them where there are two or more basement storeys each of at least 900 square metres. Volume 2 paragraph 5.38 says that in basements and enclosed car parks the lift should be within the enclosure of a protected stairway. Otherwise it should be approached only through a protected lobby or protected corridor of at least REI 30. Volume 1 paragraph 3.105 says the same for dwellings and now also allows the lift to sit within an evacuation shaft.
Car parks under flats need care at the stair. Volume 1 paragraph 3.76 says a common stair that forms part of the only escape route from a flat should not serve a covered car park, except in small single stair buildings. For those buildings paragraph 3.32(c) makes it a condition that the stair does not connect to a covered car park unless the car park is open-sided. Where a stair serves an enclosed car park, paragraph 3.78 says the lobby or corridor should have at least 0.4 square metres of permanent ventilation or be protected from smoke by a mechanical smoke control system.
Electric vehicles and charging in covered car parks
The main official document is Covered car parks: fire safety guidance for electric vehicles (opens in a new tab), from the Office for Zero Emission Vehicles (OZEV). It was published on 11th July 2023 and last updated on 8th February 2024. It applies to England and is written for operators, designers, risk assessors and owners of covered car parks.
It has interim status because it is based on the research and evidence currently available on electric vehicle fires. It says it is not a legal compliance document. There is no liability or sanction for duty holders who do not follow it. It does not replace existing safety regulations or the need to comply with them.
It covers underground, enclosed and open-sided car parks but not residential garages. It says most evidence so far suggests fires in electric vehicles are less likely than in hybrid, petrol or diesel vehicles. The risks it describes include reignition hours or days after the first fire, gas venting that can cause flash fires or jet flames, longer firefighting and more toxic smoke and run-off.
On smoke it does not set new rates. It says the volume of smoke from an electric vehicle fire is not significantly different from that of a conventional vehicle. A higher air change rate for a mechanical system or a larger ventilation area for a natural one may still be considered. Car parks that rely on a bespoke smoke ventilation design to show tenable conditions should review whether the safety measures are still adequate for electric vehicle fires. The fire risk assessment should also consider how long a mechanical system can run on back-up power.
On structure it notes that it could take up to 60 minutes for the fire service to extinguish the fire. It says a minimum of 60 minutes fire resistance should be considered unless water-based suppression is also installed or extensive fire damage can be tolerated without impacting the life safety of occupants or firefighters. Where smoke ventilation and automatic suppression work together, the order of operation needs care so that the ventilation does not delay the suppression.
Before chargepoints are installed, it says a competent person should undertake a fire risk assessment of the car park to assess their impact on existing fire safety measures.
Charging infrastructure itself is regulated by Part 9B of the Building Regulations 2010 (opens in a new tab), in force in England since 15th June 2022. Where parking is in a covered car park, meaning spaces beneath a roof other than a carport or residential garage, it requires cable routes rather than chargepoints in set cases. The OZEV guidance confirms that chargepoints can still be installed voluntarily in new or existing buildings.
The National Fire Chiefs Council's position statement on fire risks in energy technologies (opens in a new tab) calls for updates to Approved Documents S and B, including stricter sprinkler and structural requirements. It is a call for change, not guidance in force.
Proposed changes and the rest of the UK
The Building Safety Regulator's consultation on its review of Approved Document B (opens in a new tab), published with MHCLG, opened on 25th March 2026 and closed on 1st July 2026. For multistorey open-sided car parks from 5 to 18 metres it proposed raising fire resistance from 15 minutes to 30 minutes. Above 18 metres it proposed raising it from 15 minutes to 60 minutes. It said the changes would help implement other government policies, such as the safe rollout of electric vehicles.
It put the overall impact of the preferred option at £79.6 million over 10 years. A sprinkler-based alternative, with a 10 year present value cost of £242 million, was not preferred. The government's Grenfell progress report of September 2026 (opens in a new tab) says recommendations are expected by March 2027. These are proposals only. The current Table B2 periods apply until any change is made.
The consultation cites the Liverpool Echo Arena and Luton airport car park fires. It also says existing car parks are overseen and maintained under the Fire Safety Order and that there is no evidence to suggest they are inherently unsafe.
Approved Document B applies to England. Wales has its own Approved Document B. Its car park text should be read in its own right. In Scotland the non-domestic Technical Handbook (opens in a new tab) defines an open sided car park as one designed for passenger or light goods vehicles of no more than 2,500 kilograms gross and naturally ventilated in accordance with section 3. Clause 2.D.3 gives alternative guidance for the steel frame of an open sided car park whose topmost storey is no more than 18 metres above ground.
Car park ventilation ties into the structure, the stairs and lifts above and the charging strategy. Our smoke control and evacuation modelling service designs and justifies car park smoke ventilation. Our guide to smoke control in buildings covers stairs and corridors.
Sources
This guide was written from these official sources. Check the current version before relying on any figure.
- Approved Document B: fire safety, GOV.UK (official source, opens in a new tab)
- Approved Document B Volume 2: Buildings other than dwellings (official source, opens in a new tab)
- Approved Document B Volume 1: Dwellings (official source, opens in a new tab)
- Approved Document F Volume 2: Buildings other than dwellings (official source, opens in a new tab)
- Covered car parks: fire safety guidance for electric vehicles, OZEV (official source, opens in a new tab)
- Covered car parks: fire safety guidance for electric vehicles (PDF) (official source, opens in a new tab)
- Building Regulations 2010, Part 9B (official source, opens in a new tab)
- Review of Approved Document B: fire safety guidance, consultation (official source, opens in a new tab)
- Grenfell Tower Inquiry government progress report, September 2026: the construction industry (official source, opens in a new tab)
- Fire Risks in Energy Technologies, NFCC position statement (official source, opens in a new tab)
- Building Standards Technical Handbook, non-domestic, April 2026 (official source, opens in a new tab)