In England, Approved Document B gives three layouts for a single storey flat more than 4.5 metres above ground. They are a protected entrance hall, an alternative exit or a plan with a 9 metre maximum travel distance and cooking away from the entrance. Those doing the work are responsible for showing that any other layout is no less safe.

Last reviewed
Reading time
14 minutes
Related service
Fire Engineering
Geometric balconies on an apartment facade

What Approved Document B means by an open plan flat

In England the guidance for flats sits in Approved Document B (opens in a new tab) Volume 1, which deals solely with dwellings. Section 3 covers means of escape from flats under requirement B1. Paragraphs 3.6 to 3.23 deal with escape within each flat.

Approved Document B does not define an open plan flat. The nearest term, open spatial planning in Appendix A, means something else: more than one storey or level contained in one undivided volume, such as split-level floors. The practical questions are about inner rooms, the protected entrance hall and the travel distance from the furthest point of the flat to its front door.

Those details matter because of what Section 3 assumes. Paragraph 3.2 says any fire is likely to be in a flat, there is no reliance on external rescue and simultaneous evacuation of all flats is unlikely to be necessary due to compartmentation. Paragraph 3.3 says the provisions support a stay put strategy, based on a fire being contained in the flat of origin. The internal layout is what lets the people in that flat get out past a fire in their own home.

Our fire engineering service deals with layouts that do not fit the guidance. The first step is to check whether the layout already fits one of the arrangements given.

The terms that decide the layout

Four definitions in Appendix A of Volume 1 do most of the work. The first catches people out because it counts a kitchen as a habitable room.

  • Habitable room: a room used or intended to be used for people to live in. For Approved Document B this includes a kitchen but not a bathroom.
  • Inner room: a room from which escape is possible only by passing through another room, called the access room.
  • Protected entrance hall or landing: a hall or space in a flat that is enclosed with fire resisting construction other than an external wall.
  • Alternative exit: one of two or more exits, each of which is separate from the other.

Paragraph 3.7 limits which rooms may be inner rooms. A kitchen, a laundry or utility room, a dressing room and a bathroom, WC or shower room may all be inner rooms. So may any room on a storey no more than 4.5 metres above ground that has an emergency escape window. A gallery that complies with paragraph 3.13 may also be one.

A bedroom opening off a living room on a storey more than 4.5 metres above ground is therefore an inner room outside that list, unless the flat has an alternative exit as option c below describes. Paragraph 3.8 accepts an inner inner room only where the room itself complies with paragraph 3.7, each access room has a smoke alarm and none of the access rooms is a kitchen.

Flats where no storey is above 4.5 metres

For flats with upper storeys a maximum of 4.5 metres above ground level, paragraph 3.14 says the internal arrangement should follow paragraphs 3.15 to 3.17 or alternatively paragraphs 3.18 to 3.22. On the ground storey every habitable room other than a kitchen should open directly onto a hall leading to a final exit or have an emergency escape window or door. On an upper storey up to 4.5 metres each such room should have an emergency escape window or external door. In a multi-storey flat it can instead have direct access to a protected internal stairway of minimum REI 30.

Paragraph 3.17 lets two rooms share one escape window if a door between them gives access to it without passing through the stair enclosure. The common parts can still decide the matter. Paragraph 3.14 warns that where a flat is reached through the common parts of a block it may be necessary to provide a protected entrance hall to meet paragraph 3.32 and Diagram 3.9.

In small single stair buildings with no more than two flats per storey, Diagram 3.9 says the lobby between the common stair and the flat entrance is not essential if the flats have protected entrance halls. Where that lobby is left out, an automatic opening vent of at least 1m² is required at the top of the stair. Removing the protected hall in that kind of block takes away the reason the lobby could be omitted. Our guide to smoke control in buildings covers the common stair.

The three layouts for a flat above 4.5 metres

Where a single storey flat has a storey more than 4.5 metres above ground level, paragraph 3.18 says one of three approaches should be adopted. The inner room limits in paragraphs 3.7 and 3.8 still apply to each of them.

Approved Document B Volume 1 paragraph 3.18: internal planning of single storey flats above 4.5 metres (England)
OptionWhat the guidance describesFigures given
(a) Protected entrance hall (Diagram 3.2)A protected entrance hall serving all habitable rooms, each with direct access to the hallHall enclosure minimum REI 30, fire doorsets minimum E 20, a 9m maximum dimension shown within the hall
(b) Restricted travel distance (Diagram 3.3)No protected hall. The flat is planned around distance and the position of the cookingTravel distance from the flat entrance door to any point in any habitable room a maximum of 9m. Cooking facilities remote from the main entrance door and not impeding the escape route from anywhere in the flat
(c) Alternative exit (Diagram 3.4)A second way out of the flat, in the part of the flat that contains the bedrooms (paragraph 3.19)Bedrooms separated from the living accommodation by fire resisting construction of minimum REI 30 and fire doorsets of minimum E 20

Option b is the closest the guidance comes to an open plan flat. Diagram 3.3 shows a kitchen area within the open space and marks the distance to a bathroom as not restricted. A compact flat with the hob beside the front door does not meet option b, even if every point is within 9 metres.

In option a, bathrooms do not need fire doorsets provided they are separated from the adjacent rooms by fire resisting construction. Appendix C paragraph C5 says fire doorsets within flats do not need self-closing devices. The Approved Document B FAQ (opens in a new tab) adds that the recommendation for the doorsets remains, as does the advice that doors should be kept shut, especially at night.

For option c, paragraph 3.22 says the alternative exit should be remote from the main entrance door. It should lead to a final exit through a door to an access corridor, access lobby, common balcony, common stair, external stair or escape route over a flat roof. An internal private stair to an access corridor, lobby or balcony on another level is also accepted. Diagram 3.4 notes that the bedrooms are not classed as inner rooms because escape is possible in two directions.

Multi-storey flats and galleries

A multi-storey flat with its own entrance at ground level is similar to a dwellinghouse and is planned under Section 2 (paragraph 3.20). Without its own ground level entrance, paragraph 3.21 gives four approaches.

  • Approach 1: an alternative exit from each habitable room that is not on the entrance storey (Diagram 3.5).
  • Approach 2: an alternative exit from each storey other than the entrance storey, with all habitable rooms opening onto a protected landing (Diagram 3.6).
  • Approach 3: a protected stairway plus a sprinkler system in accordance with Appendix E, with smoke alarms as Section 1 describes.
  • Approach 4: where the vertical distance between the entrance storey and any other storey is no more than 7.5 metres, a protected stairway, additional smoke alarms in all habitable rooms and a heat alarm in any kitchen.

In Approach 3 sprinklers form part of a layout the guidance already accepts. That is different from using sprinklers to compensate for a departure, which is covered below.

Paragraph 3.13 says a gallery should have an alternative exit, an emergency escape window where the gallery floor is no more than 4.5 metres above ground or the conditions in Diagram 3.1. Those conditions include cooking facilities that are enclosed with fire resisting construction or remote from the gallery stair.

Every dwelling should have a fire detection and alarm system to at least Grade D2 Category LD3 under BS 5839-6. Paragraph 1.1 adds that a higher standard should be considered where occupants would be at special risk from fire.

What falls outside the guidance

Take a hypothetical sixth floor flat with a long open living and kitchen space, the hob near the front door and two bedrooms opening off the living room. The furthest point is more than 9 metres from the entrance and the bedrooms are inner rooms with no alternative exit. It meets none of the three options.

Approved Document B does not say that a layout like this must be fire engineered. Nor does it rule the layout out. The approved documents set out what may be accepted in ordinary circumstances as one way to comply. Paragraph 0.4 adds that particular attention should be given where one part of the guidance is not fully followed, as this could have a negative effect on other provisions.

The guidance offers these routes for a departure.

  • Paragraph 0.9: alternative methods may be adopted. The overall level of safety should not be lower than the approved document provides and it is the responsibility of those undertaking the work to demonstrate compliance.
  • Paragraph 0.12: fire safety engineering might provide an alternative approach. It may also be suitable for solving a specific problem with a design that otherwise follows the document. Paragraph 0.13 says BS 7974 and its supporting documents provide a framework.
  • Appendix E paragraph E4: if the provisions in a building vary from the document, sprinkler protection can sometimes be used as a compensatory feature. BS 9251 makes additional recommendations when sprinklers are proposed that way.

Paragraph 0.9 also allows another standard or guidance document to be used, provided its relevant fire safety recommendations are followed in their entirety. Approved Document B does not point to an open plan clause in BS 9991. The only BS 9991 clause Volume 1 points to is clause 7.3, which paragraph 3.33 allows to modify paragraph 3.27 for flats with balcony or deck access. Our guide to BS 9991, BS 9999 or Approved Document B explains how choosing a whole code works.

Asked whether providing sprinklers in a block of flats allows other fire protection measures to be reduced, the FAQ says this would be a matter for the designer and the relevant building control body to consider. It warns that any such proposal may result in the need to upgrade the sprinkler specification and the duration of the water supplies.

How a departure is justified

A departure is a design decision that has to be shown to work. Our guide to what a fire engineered solution is covers the method in general. For a flat layout the case normally follows these steps.

  • Identify exactly which provision is not met, such as the 9 metre limit, the position of the cooking or an inner room.
  • Agree the approach with the building control body at an early stage, as the approved documents advise.
  • Set out what compensates for the departure, for example sprinklers to BS 9251 under Appendix E.
  • Show that the combined design gives an overall level of safety no lower than the guidance provides.
  • Check the effect on the common parts, including any lobby or vent arrangement that depends on protected entrance halls.
  • Avoid relying on residents behaving in a particular way. Paragraph 0.6 says reliance on an unrealistic or unsustainable management regime cannot be considered to have met the requirements.
  • Record the departure and its compensation in the fire strategy, which Section 17 says should be made available at handover. Our guide to Regulation 38 covers that duty.

Sprinklers are already expected in many new blocks. Paragraph 7.4 says blocks of flats with a top storey more than 11 metres above ground level should have a sprinkler system throughout in accordance with Appendix E, provided within the individual flats. Leaning on that same system to justify a flat layout raises the question the FAQ answer above deals with. Our guide to sprinklers in blocks of flats covers the 11 metre rule.

The London Fire Brigade's fire engineering thematic reports (opens in a new tab), released under freedom of information, give some context from London. Its Q2 2020 report said sprinklers used as a compensatory feature for departures within flat layouts were often misunderstood, in particular where a protected entrance hall exceeded the 9 metres permissible in guidance. The series stopped after 2021 and these are historical observations, not guidance.

Knocking through walls in an existing flat

Opening up a kitchen and living room in an existing flat is not only a design question. Under regulation 3 of the Building Regulations 2010 (opens in a new tab) an alteration is material if it would at any stage leave a building not complying with a relevant requirement where previously it did. The relevant requirements include B1 (means of warning and escape) and B3 (internal fire spread, structure). Removing a protected hall can therefore make the work a material alteration.

The Local Government Association guide Fire safety in purpose-built blocks of flats (opens in a new tab), hosted on GOV.UK, describes the problem in existing blocks. One of its examples is a resident removing the doors and walls to the kitchen and lounge to create an open-plan living area. That makes all the bedrooms inner rooms and can impair protection to the common parts. The guide says it is not uncommon for occupants to remove internal doors or partitions.

Where residents have done so, it says reinstating the fire doors and partitions will ensure adequate means of escape. This may be necessary to protect the common means of escape where the building depends on the protection of the internal hallway. The guide dates from 2011 and its cover note says it should be viewed as no longer comprehensive. Our guide to keeping a fire strategy up to date covers alterations more widely.

Wales and Scotland

The three nations treat flat layouts differently. Wales gives broadly the same options under different paragraph numbers. Scotland states an open plan option in its guidance.

Internal planning of flats in England, Wales and Scotland
NationGuidanceWhat it says
EnglandApproved Document B Volume 1, paragraph 3.18Three approaches for a single storey flat above 4.5m: a protected entrance hall, a 9m travel distance with cooking remote from the entrance or an alternative exit. Departures under paragraphs 0.9 and 0.12 and Appendix E4
WalesWelsh Approved Document B Volume 2, paragraphs 3.13 to 3.16Three acceptable approaches for a flat with a floor more than 4.5m above ground: a protected entrance hall with 9m or less from the entrance door to the door of any habitable room, a 9m travel distance with cooking remote from the entrance door or an alternative exit. Paragraph 3.16 covers multi-storey flats
ScotlandDomestic Technical Handbook, April 2026, clause 2.9.7An open plan option for escape within dwellings, provided the kitchen is remote from the exit door. Where the topmost storey is more than 4.5m above ground, an automatic life safety fire suppression system to BS 9251: 2014 and a Grade D, Category LD1 enhanced early warning system to BS 5839: Part 6: 2019 should be installed

In Wales flats are covered by Volume 2 of the Welsh Approved Document B (opens in a new tab), not Volume 1. See our Wales page for projects there.

Clause 2.9.7 of the Scottish domestic Technical Handbook (opens in a new tab) names the open plan option directly. See our Scotland page for projects there.

Wherever the flat is, the quickest route is to test the layout against the guidance first and engineer only the part that does not fit. Our fire engineering team prepares that case and sets out to agree it with building control (the verifier in Scotland) before the layout is fixed.

Sources

This guide was written from these official sources. Check the current version before relying on any figure.

Common questions

More on this topic.

All fire strategy questions

In England, yes, if the layout fits Approved Document B. For a single storey flat above 4.5 metres, option b of paragraph 3.18 accepts a layout without a protected entrance hall where every point in every habitable room is within 9 metres of the entrance door and the cooking is remote from that door. A layout that fits none of the guidance arrangements is an alternative approach, which the guidance says should be agreed with the building control body early.

Keep reading

Related guides.

Talk to an engineer

Tell us about the building

Send us the drawings, the building type and the stage you are at. We reply the same day with a clear scope, programme and fixed fee.

  • 01Written in-house by the engineer who will defend it to the approver
  • 02Approved Document B, BS 9999, BS 9991 and BS 7974
  • 03Building Control and fire authority engagement handled for you
  • 04Projects of every size, across the UK

Request a quote

Same-day reply

Only used to reply to this enquiry.

We reply the same day.