In England, fire safety works that would affect a listed building's special character need listed building consent before they start. Historic England says that can include alarms, emergency lighting and replacement fire doors. Approved Document B says some variation of its provisions may be appropriate in historic buildings, based on the hazard and risk in each case.

Last reviewed
Reading time
14 minutes
Related service
Fire Strategy Reports
A brick mill beside the River Derwent in Derby

What Approved Document B says about historic buildings

Listed buildings are not exempt from the Building Regulations. Historic England's building regulations page (opens in a new tab) says so directly, while noting that some approved documents recognise the special needs of historic buildings. It also says existing buildings are not generally required to be brought up to newer standards. It says Part B applies to all material changes of use set out in regulation 5. It also says many fire safety measures do not need building regulation approval.

Approved Document B Volume 2 (opens in a new tab) paragraph 0.17 says that where Part B applies to existing buildings, particularly those of special architectural or historic interest for which its guidance might prove too restrictive, some variation of its provisions may be appropriate. In such cases it is appropriate to assess the hazard and risk in the particular case and consider a range of fire safety features in that context. Volume 1 (opens in a new tab) paragraph 0.10 says the same for dwellings.

Volume 1 paragraph 2.22 deals with doors in loft conversions. Where it is undesirable to replace existing doors because of historical or architectural merit, it says the possibility of retaining them and upgrading them where necessary should be investigated. Our guide to loft conversion fire safety covers the rest of that work.

Two limits apply. Approved Document B says guidance written for assessing existing buildings often contains less onerous provisions than for new buildings. It is therefore unlikely to be appropriate for building work controlled by the regulations. It also says reliance on an unrealistic or unsustainable management regime cannot be considered to meet the regulations. A variation should rest on real compensating features and a management regime the owner can sustain.

The fire service, fire risk assessors and the Fire Safety Order

Historic England says single private dwellings, which make up the majority of listed buildings, are generally outside the Regulatory Reform (Fire Safety) Order 2005. Hotels, houses in multiple occupation, flats and care homes are within it in whole or in part.

Where the Order applies, article 30 (opens in a new tab) says that before serving an enforcement notice that would oblige a person to alter premises, the enforcing authority must consult any other person whose consent to the alteration would be required by law. Historic England reads this as requiring the fire and rescue service to consult the local planning authority conservation officer. It says fire and rescue services and fire risk assessors working in listed buildings should advise the owner or responsible person that listed building consent may be required before any interventions are put in place.

The Home Office residential care guide (opens in a new tab), which applies to England, makes the same point in its Appendix C. It says the advice or consent of building control and other relevant bodies should form part of any fire risk assessment that affects the character of the building, such as replacing doors, fittings, panelling and decor or material changes to existing escape routes. It says an ideal solution is one that is reversible, enabling the historic elements to be reinstated.

The guide lists alternatives to conventional precautions. They include a fire engineering solution, upgrading existing doors and partitions sympathetically and specialist detection or suppression systems. Where the building cannot take conventional features, it says the building has to be managed by limiting occupant numbers and activities and by providing adequate supervision.

Historic doors

Historic England says its most common fire enquiry comes from owners told to replace their doors with fire doors that have a current test certificate. It quotes government fire door guidance on the Fire Safety (England) Regulations 2022, which says the absence of intumescent strips, smoke seals or certification does not imply that a door is unfit for purpose. Historic England recommends that this is considered before any heritage door is altered or replaced.

Its advice for fire safety professionals says each door should be assessed while the fire strategy is being written. The assessment decides whether the door needs to be a fire door, a smoke stop door or neither. It weighs the door's historical and architectural significance against its likely fire resistance and examines whether it can be upgraded. Once a door has been assessed in a fire strategy, reassessment should not be necessary unless its condition, use or circumstances have materially changed.

Historic England's Guide to the Fire Resistance of Historic Timber Panel Doors (opens in a new tab), published on 1st July 2021, sets out how to decide whether changes are needed and how far a door can be upgraded. Its upgrading section is limited to single swing panel doors. Intumescent paints and varnishes were left out because of variations in how they are applied.

Historic England says the possibility that consent to replace doors is refused should be considered. A strategy that depends on replacing every door has no fallback if consent is refused.

Compartmentation, floors and concealed voids

Historic England lists improving compartmentation among the interventions that need to be undertaken with caution so that the heritage value of the building is not irreparably damaged. Concealed spaces need particular attention. GN80 (opens in a new tab), version 07 of 20th June 2025, says compartment walls in many historic buildings were not built up into the roof space. It calls compartmentation of the roof void a vital element in improving fire performance. Barriers that do not line up with the compartment lines below will undermine the building's fire integrity. It says lath and plaster and timber panelling create narrow continuous cavities that are among the most vulnerable elements. It says a full compartmentation survey may be appropriate. Our guide to compartmentation and fire stopping explains the principles.

GN80 accepts that upgrading a floor can mean some loss of historic fabric. It lists recognised methods.

  • Mineral fibre quilt between or below the joists
  • Intumescent sheet over or under existing surfaces
  • Intumescent material at the floor perimeter
  • Intumescent coatings to ceilings
  • Additional fire-resistant boards to ceilings or floors

Choosing between them is a heritage decision as much as a fire one. Working from above may protect a decorated ceiling, while working from below may protect historic boards. Recording the reason for the choice helps the conservation officer judge it.

Detection, suppression and hot works

Historic England's advice for owners (opens in a new tab) recommends that all heritage buildings have an appropriate fire detection and alarm system for early warning. It says most non-domestic buildings should follow BS 5839-1 and single private dwellings, houses in multiple occupation and flats BS 5839-6. Early warning protects the fabric as well as the occupants.

Historic England's list of active measures includes water-based suppression such as sprinklers, deluge or spray, misting and foam, as well as gas systems. Suppression can let a design keep features that would otherwise have to change. Each system brings pipework, heads and water supplies that may need consent and careful routing.

Works themselves are a fire risk. GN80 says the risk of fire increases significantly during refurbishment or alteration. Historic England advises that hot works such as cutting, welding or soldering should not be carried out in historic buildings unless there is absolutely no alternative. It says many serious fires in historic buildings have been caused by contractors using blow lamps or naked flames. It has an advice note on permit to work systems.

Historic England's research identified more than 1,000 fire incidents in 2019 involving heritage assets that needed fire and rescue service attendance. Its fire advice (opens in a new tab) says the safe evacuation of occupants must take precedence over measures to protect the property. It also suggests owners consider preparing and testing a salvage emergency plan. Its advice pages for fire safety professionals and for owners were last updated on 11th September 2026.

Using a fire strategy and fire engineering

Historic England's advice for fire safety professionals (opens in a new tab) says a fire strategy should be considered for larger or more complex heritage buildings. It would record the overall approach and provide the basis for later fire risk assessments. Measures already assessed and justified could then be taken into account, provided the building, its use and the measures have not materially changed. It says the strategy should include passive and active measures.

Historic England lists what can be used to assess the building. They are any former fire certificate and plans, verified against the building as it is today, the fire safety guides published under the Fire Safety Order, BS 9999:2017, BS 9991:2024, Approved Document B and a fire engineered solution based on BS 7974:2019. Where an existing building has no strategy, our guide to retrospective fire strategies explains how one is produced.

Approved Document B paragraph 0.18 says fire safety engineering might provide an alternative approach and may be the only practical way to achieve a satisfactory standard in some complex buildings. GN80 says that in certain instances it is the only practical way for a historic building to comply with the Order and the Building Regulations. It says the responsible person should seek guidance from a qualified and competent fire engineer. Our guide to fire engineered solutions explains how that case is made.

GN80 also says no variation to the premises should take place without a full review of the fire risk assessment or fire strategy, with any deviation from guidance fully documented. That applies with extra force on a change of use, where Historic England notes that the change may adversely affect other parts of the building, for example in relation to fire safety. Healthcare buildings have a further layer of guidance. HTM 05-03 Part J lists heritage among the other fire safety objectives an engineered healthcare design can include. Our guide to HTM 05-02 covers the healthcare guidance.

Wales and Scotland

Listed building law differs in each nation and the differences matter for which Act is cited in an application.

Listed building consent law by nation, as at 23rd November 2026
NationLawKey provisions
EnglandPlanning (Listed Buildings and Conservation Areas) Act 1990Listing under section 1, works controlled by section 7, consent under section 8, offence under section 9
WalesHistoric Environment (Wales) Act 2023, in force for listed buildings since 4th November 2024Listing under section 76, works controlled by section 88, consent under section 89, offence under section 117
ScotlandPlanning (Listed Buildings and Conservation Areas) (Scotland) Act 1997Works affecting character controlled by section 6

In Wales, section 88 (opens in a new tab) of the 2023 Act says a person must not carry out works for the alteration or extension of a listed building in any way that would affect its character unless the works are authorised under section 89. The same applies to demolition. Section 117 (opens in a new tab) makes a breach an offence, with the same four-part urgent works defence as the 1990 Act. Cadw (opens in a new tab) says consent is administered by local planning authorities and may be needed for relatively minor work such as replacing an external door. A heritage impact statement must accompany the application. Cadw's Managing Change to Listed Buildings in Wales dates from May 2017, before the 2023 Act. It says listed building consent is separate from planning permission and building regulations approval. Cadw's website had no guidance specific to fire safety when checked on 23rd November 2026.

Welsh Government TAN 24 (opens in a new tab), March 2026, says at paragraph 5.32 that local authorities should exercise their responsibilities for the safety of listed buildings under the building regulations and fire legislation with sympathy when repair and conversion are proposed. It says they should try to balance those objectives against the building's special interest. The Welsh Approved Document B Volume 2 paragraph 0.33 allows the same kind of variation as the English guidance. Wales also requires automatic fire suppression in new and converted care homes, residential rooms and dwellings under regulation 37A (opens in a new tab) of the Building Regulations 2010. Regulation 37A(4) says this does not apply to buildings listed under section 76 of the 2023 Act, in a conservation area designated under section 158 or included in the schedule of monuments under section 3, where installing a fire suppression system would unacceptably alter their character or appearance. See our Wales page.

In Scotland, section 6 (opens in a new tab) of the 1997 Act controls works affecting a listed building's character. Historic Environment Scotland's Managing Change: Fire and Historic Buildings (opens in a new tab), published on 31st October 2023, is non-statutory but a material consideration in listed building consent decisions. It says interior works will need consent if they affect the building's character. See our Scotland page.

In every nation the approach is the same. Understand what is significant, assess the real fire risk, then choose the measures that protect life with the least harm to the fabric. Our fire strategy reports and fire engineering service set out that reasoning for the conservation officer and the building control body together.

Sources

This guide was written from these official sources. Check the current version before relying on any figure.

Common questions

More on this topic.

All fire strategy questions

Historic England says consent for replacing doors in listed buildings will probably be required. It recommends considering whether existing doors can be kept and upgraded before any are altered or replaced.

Keep reading

Related guides.

Talk to an engineer

Tell us about the building

Send us the drawings, the building type and the stage you are at. We reply the same day with a clear scope, programme and fixed fee.

  • 01Written in-house by the engineer who will defend it to the approver
  • 02Approved Document B, BS 9999, BS 9991 and BS 7974
  • 03Building Control and fire authority engagement handled for you
  • 04Projects of every size, across the UK

Request a quote

Same-day reply

Only used to reply to this enquiry.

We reply the same day.