In England, Approved Document B Volume 1 paragraph 2.21 says a loft conversion that creates a storey above 4.5 metres should address the full extent of the escape route, with E 20 fire resisting doors and REI 30 partitions. A fire detection and alarm system with mains operated smoke alarms should be fitted. Building regulations approval is required.

Last reviewed
Reading time
11 minutes
Related service
Fire Strategy Reports
A brick terrace of houses in Islington

Does a loft conversion need building regulations approval?

Yes, in England and in Wales. The Planning Portal (opens in a new tab) says building regulations approval is required to convert a loft or attic into a liveable space. The regulations check that the new floor is strong enough, that the stability of the structure and existing roof is not endangered and that there is safe escape from fire. They also cover safely designed stairs to the new floor and reasonable sound insulation between the conversion and the rooms below.

The Planning Portal guidance is written for the loft of an existing house no more than two storeys high. It says requirements for flats, maisonettes or houses over three storeys will be similar but may be more extensive and may extend to other parts of the building. It recommends contacting a building control body, usually the local council, to discuss the proposal. You must also find out whether the work falls within the Party Wall etc. Act 1996.

Even boarding out a loft for storage can need approval. The Planning Portal says existing joists will not have been designed to support a significant weight. Laying floorboards over them may mean applying to a building control body for building regulations approval.

Where a loft design departs from the Approved Document B guidance, for example to keep an open-plan layout without the listed alternatives, our fire strategy reports set out the case for building control. Our guide to whether you need a fire strategy explains when one is expected.

Why a new storey above 4.5 metres changes the rules

Approved Document B Volume 1 (opens in a new tab) treats upper storeys up to 4.5 metres above ground differently from those above it. Up to 4.5 metres in a house served by one stair, paragraph 2.2 says each habitable room other than a kitchen should have an emergency escape window or external door. Direct access to a protected stairway is the alternative. Above 4.5 metres the route out is a protected stairway or an alternative escape route under paragraph 2.5. The Planning Portal explains why. It says it is too dangerous to escape via windows from floors above first floor level.

Paragraph 2.21 is the core rule for loft conversions. Where a new storey is added through conversion to create a storey above 4.5 metres, the full extent of the escape route should be addressed. Fire resisting doors (minimum E 20) and partitions (minimum REI 30) should be provided, including upgrading the existing doors where necessary.

The phrase full extent of the escape route is the part people miss. The Planning Portal says escape provisions need to be considered throughout the route. That often means extra fire protection in the existing parts of the house. For a typical loft conversion to a two storey house, it says the result is new fire-resisting doors and sometimes partitions to protect the stairway.

Approved Document B FAQ 26 makes the same point for upward extensions. Some work on the original part of a building is likely to be necessary where storeys are added. Regulation 4(3) requires that the level of fire protection in the building as a whole is made no worse.

The protected stairway

For a house with one storey above 4.5 metres, paragraph 2.5a describes a protected stairway separated by fire resisting construction (minimum REI 30) at all storeys. It should either extend to a final exit or give access to at least two ground level final exits separated from each other by REI 30 construction and E 20 fire doorsets. Cavity barriers or a fire resisting ceiling (minimum EI 30) should be provided above the protected stairway enclosure.

Paragraph 2.5b offers an alternative. The top storey can be separated from the lower storeys by REI 30 construction and given an alternative escape route leading to its own final exit.

Where a conversion leaves the house with two or more storeys above 4.5 metres, paragraph 2.6 asks for more. In addition to the protected stair, either each storey more than 7.5 metres above ground should have an alternative escape route or a sprinkler system should be provided throughout to BS 9251. Diagram 2.1 says no inner rooms are allowed on those storeys.

Paragraphs 2.7 to 2.9 cover services. A passenger lift serving a storey above 4.5 metres should be in the protected stair enclosure or in a fire resisting lift shaft (minimum REI 30). Transfer grilles should not be fitted in any wall, door, floor or ceiling of the stair enclosure.

Fire doors on the escape route

The doors onto the protected stair should be at least E 20, which means 20 minutes' integrity. Existing doors may need upgrading. Approved Document B FAQ 4 says a fire doorset should be regarded as a complete installed assembly. In most cases it should still be possible to retain the existing frame.

The FAQ lists what often needs attention. Door stops may need replacing or relocating. The joint between frame and wall should be adequately fire stopped. The gap between door and frame should be kept to a minimum, usually 3 to 4mm. Upgrading the leaf alone and ignoring the frame, stops and fixings misses the point of a complete assembly.

Fire doorsets within dwellinghouses do not need a self-closing device. Appendix C paragraph C5 makes that exception, along with cupboards and service ducts normally locked shut. Paragraph C4 says test evidence must apply to the complete installed assembly.

The FAQ also says it may not always be necessary to fit fire doorsets to cupboards if they are small and the fire risk is low. An alternative to a fire doorset on a bathroom is to include the bathroom within the stair enclosure. Where existing doors have historical or architectural merit, paragraph 2.22 says the possibility of retaining and upgrading them should be investigated.

Keeping an open-plan ground floor

Many houses have had the hall opened into the living space. The note to paragraph 2.21 says that where the layout is open plan, new partitions should be provided to enclose the escape route. Paragraph 2.23 sets out an alternative package for those who want to keep the open plan.

  • Sprinkler protection to the open-plan areas
  • A fire resisting partition (minimum REI 30) and door (minimum E 20) separating the ground storey from the upper storeys, with the door allowing occupants of the loft room to reach a first storey escape window
  • Cooking facilities separated from the open-plan area by fire resisting construction (minimum REI 30)

The partition and door separate the ground storey from the floors above. Occupants of the loft room can then reach a first storey escape window if the open-plan ground floor is affected by fire. A design that keeps the open plan without this package needs a justified alternative agreed with building control. Our fire engineering service prepares that case. For flats, the equivalent layouts are covered in our guide to open-plan flats.

Escape windows

Escape windows still matter in a loft project on any storey up to 4.5 metres, which usually includes the first floor. Paragraph 2.10 sets the minimum standard. People escaping should be able to reach a place free from danger from fire. Locks and stays with child-resistant release catches may be fitted. The window should be capable of remaining open without being held.

  • An unobstructed openable area of at least 0.33 square metres
  • A minimum height of 450mm and a minimum width of 450mm
  • The bottom of the openable area a maximum of 1100mm above the floor

Inner rooms are allowed on a storey up to 4.5 metres if they have an escape window, under paragraph 2.11. Paragraph 2.12 accepts an inner inner room only if the access rooms each have a smoke alarm and none of them is a kitchen.

Replacing windows needs care. Paragraphs 2.19 and 2.20 say that where an existing window would be an escape window, the replacement should give at least the same potential for escape. Replacing windows may also need cavity barriers around the opening in line with Section 5.

Smoke and heat alarms

Paragraph 1.8 says a fire detection and alarm system should be installed where a new habitable room is provided above or below the ground storey. A loft room meets that test. Paragraph 1.9 says smoke alarms should be provided in the circulation spaces of the dwelling in line with paragraphs 1.1 to 1.4.

Those paragraphs set a minimum of Grade D2 Category LD3 in accordance with the relevant recommendations of BS 5839-6. Smoke alarms should be mains operated and conform to BS EN 14604. Heat alarms should be mains operated and conform to BS 5446-2. Both should have a standby power supply such as a battery or capacitor.

The Planning Portal fire safety page (opens in a new tab) says mains powered, interlinked smoke alarms will need to be provided within the stairway at each level. Larger houses go further. Under paragraphs 1.5 to 1.7 a large dwellinghouse has more than one storey with at least one storey over 200 square metres. It needs Grade A Category LD3 with two storeys and Grade A Category LD2 with three or more.

Floors between the loft and the escape route

Paragraph 5.4 covers floors when an additional storey is added to a two storey single family dwellinghouse. New floors should have a minimum REI 30 fire resistance. Any floor forming part of the enclosure to the circulation space between the loft conversion and the final exit should achieve at least REI 30. The existing first storey construction should have a minimum rating of R 30.

The paragraph allows the integrity and insulation performance to be reduced when both of two conditions are met. Only one storey is added and it contains a maximum of two habitable rooms. The new storey also has a maximum total area of 50 square metres. Check both conditions before relying on the existing ceilings.

Planning, conversions to flats, Wales and Scotland

In England many loft conversions fall within Class B permitted development in the Town and Country Planning (General Permitted Development) (England) Order 2015 (opens in a new tab). The limits include 40 cubic metres of added roof space for a terrace house and 50 cubic metres in other cases. Permitted development does not remove the need for building regulations approval.

A loft conversion that creates a separate flat is a different project. It is a material change of use and Approved Document B Volume 1 paragraph 6.5 covers conversions to flats. Our guides to change of use and Approved Document B cover that route.

Loft conversions across the three nations
NationApprovalFire guidance
EnglandBuilding regulations approval from a building control bodyApproved Document B Volume 1 paragraphs 2.21 to 2.23 and 5.4
WalesBuilding regulations approval is requiredWelsh Approved Document B Volume 1 paragraph 3.20b for loft conversions and paragraph 5.7 for floors
ScotlandA building warrant. Using an attic as a room is a conversionDomestic Technical Handbook Section 2

In Wales the Welsh Government guide (opens in a new tab) repeats the escape route and fire door advice and the need for mains powered, interlinked smoke alarms within the stairway at each level. The Welsh Approved Document B Volume 1 (opens in a new tab) paragraph 5.7 accepts a modified 30 minute standard for the existing first floor, where it separates only rooms and not circulation spaces, if one storey of no more than two habitable rooms and not more than 50 square metres is added. Where a house already has automatic fire suppression, paragraph 3.20c says it should be extended and re-certified to include any altered, extended and additional controlled areas.

In Scotland the Domestic Technical Handbook (opens in a new tab) says developing a roof space as habitable space is a conversion in terms of regulation 4, a warrant is required and the standards also apply. Clause 2.9.4 treats windows in a storey above 4.5 metres as too high above the adjacent ground from which to escape.

If your conversion cannot follow the standard provisions, our fire strategy reports service can set out an alternative for building control. Contact us with the existing and proposed drawings.

Sources

This guide was written from these official sources. Check the current version before relying on any figure.

Common questions

More on this topic.

All fire strategy questions

In England, where the conversion creates a storey above 4.5 metres, Approved Document B recommends fire resisting doors of at least E 20 on the escape route, including upgrading existing doors where necessary. Fire doorsets within a house do not need self-closing devices.

Keep reading

Related guides.

Talk to an engineer

Tell us about the building

Send us the drawings, the building type and the stage you are at. We reply the same day with a clear scope, programme and fixed fee.

  • 01Written in-house by the engineer who will defend it to the approver
  • 02Approved Document B, BS 9999, BS 9991 and BS 7974
  • 03Building Control and fire authority engagement handled for you
  • 04Projects of every size, across the UK

Request a quote

Same-day reply

Only used to reply to this enquiry.

We reply the same day.