Progressive horizontal evacuation moves people away from a fire through a fire-resisting barrier into an adjoining protected area on the same floor. They wait there or move on to another area or a stair. It is the standard design basis for most healthcare premises under HTM 05-02 and for care homes for the elderly under Approved Document B in England.

Last reviewed
Reading time
14 minutes
Related service
Fire Strategy Reports
A white hospital corridor

What is progressive horizontal evacuation?

NHS England's HTM 05-02 (opens in a new tab) describes progressive horizontal evacuation as moving occupants from an area affected by fire through a fire-resisting barrier to an adjoining area on the same level. That area is designed to protect them from the immediate dangers of fire and smoke. The occupants may stay there until the fire is dealt with or wait for assisted onward evacuation by staff to another adjoining area or to the nearest stairway.

The point is time. HTM 05-02 says the procedure should give enough time for non-ambulant and partially ambulant patients to be evacuated vertically to a place of safety if a whole storey has to be cleared.

The evacuation strategy is one of the core decisions in a fire strategy report. It sets the layout of compartments, the fire resistance of walls and doors, the alarm and the number of staff the building needs.

Why hospitals and care homes use it

HTM 05-02 says the immediate and total evacuation of a healthcare building would be a major logistics exercise and, from a patient safety point of view, not desirable. Evacuation should instead be based on progressive horizontal evacuation, with only those directly at risk being moved. The exception is premises where all occupants are independent.

Approved Document B (opens in a new tab) in England points healthcare buildings to the Firecode guidance, which it says should be followed. For care homes for the elderly, Volume 2 paragraph 2.34 says some or all residents are likely to need help to evacuate and buildings should generally be designed for PHE. For other care home types, the most appropriate of PHE or simultaneous evacuation should be identified. The approach adopted must be recorded and communicated to the building management team.

The Home Office residential care guide (opens in a new tab) says all care premises it covers should develop a PHE strategy, other than small premises where residents can escape quickly and immediately to open air. The NFCC guidance note (opens in a new tab) of 18th November 2021 says the strategy for care and nursing homes is usually PHE. It adds that it depends on an effective emergency plan, enough well trained staff and supervisors and effective management of their actions.

Evacuation strategies in residential care, as described in the Home Office guide
StrategyHow it worksWhere it fits
Single stage evacuationEveryone leaves directly to a place of total safety in the open airSmall premises where residents can escape quickly and immediately
Progressive horizontal evacuationResidents move through a fire resisting barrier to an adjoining protected area on the same levelPremises where residents depend on staff to help them escape
Delayed evacuationResidents remain in their rooms, which have enhanced structural fire protection to the individual bedroomListed in the guide as a typical strategy alongside the other two

The three stages of evacuation

HTM 05-02 paragraph 2.7 breaks evacuation into three stages. Each stage moves people further from the fire and is used only when the stage before it is not enough.

  • Stage 1. Horizontal evacuation from the area where the fire starts to an adjoining sub-compartment or compartment
  • Stage 2. Horizontal evacuation of the whole compartment where the fire starts to an adjoining compartment on the same floor
  • Stage 3. Vertical evacuation to a lower floor or to the outside

For dependent and very high dependency patients the strategy is to move them on their bed or in a wheelchair to a refuge on the same floor. They are then taken to another floor or outside only if that becomes necessary. HTM 05-02 says vertical escape should only be carried out if a fire cannot be controlled within the space of origin and there is additional risk to people outside the compartment of origin.

Because the last stage may be needed, HTM 05-02 says areas to which patients have access should not be on storeys where evacuation would mean travelling up a stairway to a final exit. It also recognises many benefits in using lifts to assist vertical evacuation.

Hospital design under HTM 05-02

HTM 05-02 is the 2015 edition and the NHS England page says it was last updated on 4th November 2015. It covers fire safety in the design of new healthcare buildings and extensions in England. It says that, applied correctly, it will satisfy all the requirements of Part B of the Building Regulations 2010.

Firecode uses three patient dependency classes. Independent patients can leave without staff help or with minimal assistance. Very high dependency patients are those whose treatment or condition creates a high dependency on staff, such as in intensive care and operating theatres. Dependent patients are everyone else.

Each compartment should be able to hold its own occupants plus the designed occupancy of the most highly occupied adjoining compartment, including space for beds and medical equipment. Compartments containing patient access areas are divided into sub-compartments to limit the number of patients a fire can affect.

Key PHE figures in HTM 05-02 (England, 2015 edition)
ItemHTM 05-02 figureParagraph
Levels up to 12 m, under 1000 square metres, with patient accessNo more than 30 patients and at least two compartments3.8
Beds in a compartment with sleeping accommodationNo more than 203.9
Levels up to 12 m, over 1000 square metres, with patient accessAt least three compartments, one of which may be a hospital street3.11
Levels over 12 m above ground with patient accessAt least four compartments, each at least 500 square metres where there is no hospital street (350 square metres with sprinklers)3.13 and 3.14
Maximum compartment size2000 square metres multi-storey, 3000 square metres single storey5.11
Compartment wall fire resistance30 minutes for single storey and all sprinklered buildings, 60 minutes for all others5.12
When to sub-compartmentFloor area over 750 square metres, departments with more than 30 patients having access at the same time or sleeping accommodation for more than 30 patients3.25
Sub-compartment walls and exitsAt least 30 minutes fire resistance and at least two exits to separate adjoining areas3.26 and 3.27
Travel in one direction only15 m for in-patient accommodation and 18 m for all other parts3.30
Travel from any point in a sub-compartmentNo more than 30 m to an adjoining compartment, sub-compartment, stairway or final exit3.35
Mental health in-patient unitsNo more than 10 beds in any sub-compartment, including swing beds2.55

For out-patient departments in hospitals the floor area may rise to 1000 square metres before sub-compartmentation becomes necessary. Every healthcare building should have at least two stairways and the number rises with the beds on any one upper storey, from two stairways for up to 100 beds to five for 301 to 400.

A hospital street is a special compartment that connects final exits, stairway enclosures and department entrances. It lets people be moved to unaffected parts and serves the fire and rescue service as a firefighting bridgehead. HTM 05-02 says hospital streets are not an essential requirement. Where one is used it needs a clear width of at least 3 m and at least three sub-compartments each no longer than 30 m. See our healthcare and hospitals page for that sector.

Care home design under Approved Document B

Volume 2 of Approved Document B sets out PHE for care homes where the Firecode documents do not apply. PHE requires areas used for the care of residents to be divided into protected areas by compartment walls and compartment floors. A protected area is a place of relative safety from which further evacuation can be made if needed.

  • Each storey used for the care of residents is divided by compartment walls into at least three protected areas and all floors are compartment floors
  • Every protected area has at least two exits to adjoining protected areas
  • A protected area used for horizontal evacuation can hold its own occupants plus those from the largest adjoining protected area
  • Travel from any point to a storey exit or final exit is no more than 64 m
  • Travel to the exit into the next protected area follows Table 2.1, which allows 9 m where travel is in one direction only or 18 m where it is in more than one
  • No more than 10 residents' beds in one protected area, possibly fewer depending on the assessment
  • Each bedroom is enclosed in fire resisting construction of at least REI 30 with doors of at least E 30 and every corridor serving bedrooms is a protected corridor
  • Bedrooms hold no more than one single or double bed
  • Ancillary rooms such as kitchens, laundries, stores and plant rooms are enclosed in at least REI 30 construction and escape routes do not pass through them
  • A fire detection and alarm system to L1 standard under BS 5839-1
  • Free-swing door closers to bedrooms and hold-open devices in circulation spaces where self-closing doors could obstruct residents
  • A sprinkler system throughout the building in line with Appendix E

The sprinkler provision in paragraph 2.46 came in through the 2025 amendments (opens in a new tab), which took effect on 2nd March 2025 for use in England. Work notified before that date and sufficiently progressed falls under transitional arrangements.

Research published by the BSR on 22nd December 2025 says further clarity is needed on protected areas where bedrooms are in a dead end and on whether stairs can be protected areas. It says more evidence is needed on the 10 bedroom limit. This is research rather than guidance and it may lead to future change. See our care homes and retirement living page for that sector.

How long should evacuation take?

HTM 05-02 does not set an evacuation time. The 2.5 minute figures quoted for care homes come from two other sources and they measure different things.

The Home Office residential care guide says it should be possible under normal operating conditions to evacuate any given protected area in 2.5 minutes, using the staff present to help residents where necessary. It says you should aim to move all occupants of a protected area to a place of reasonable or total safety within 2.5 minutes of the alarm being raised. It calls this a starting point on which to base an assessment. You should run a simulated evacuation of each protected area assuming the worst case, which is usually when the fewest staff are on duty, such as at night when residents are asleep.

The NFCC note measures something else. It says research has shown it can take two staff about 2.5 minutes to evacuate each mobility impaired resident. It says that means potentially more than twenty minutes to evacuate all residents into an adjacent protected area corridor. It notes night staffing may be only two or three in smaller homes.

One figure is a target for clearing a whole protected area. The other is a time per resident for a pair of staff. Read together, they show why protected area size, staffing and resident dependency have to be designed together. Where movement times to the next protected area are excessive, the Home Office guide gives these options for an existing care home.

  • Reduce the size of the protected area, for example by fitting fire-resisting self closing doors across a corridor
  • Increase the number of staff
  • Accommodate fewer people
  • Provide an appropriately designed sprinkler system

It adds that fire engineering solutions may be available to compensate for extended escape time but should only be considered following the advice of an expert. Our guide to fire engineered solutions explains how that case is made.

In healthcare, HTM 05-03 Part J notes that a fire engineering study of PHE may have one RSET for evacuation between sub-compartments and another for evacuation between compartments. Our smoke control and evacuation modelling service carries out that kind of analysis.

Who is responsible for making it work?

PHE is a design and a management system at the same time. HTM 05-02 assumes there are enough adequately trained staff on duty to carry out the emergency plan. It says management responsibilities such as the area under each manager's control, fire drills and the management of evacuation will significantly affect the design, size and layout of compartments.

The design has to be recorded for the people who run the building. HTM 05-02 says a detailed record of the fire safety strategy, evacuation procedures, patient dependency and staffing levels will be required for all premises it covers. For care homes, Approved Document B says the number of beds in a protected area should rest on an assessment of the staff likely to be available and the level of help residents may need. The Regulation 38 fire safety information should include that assessment.

Once the building is occupied the responsible person owns the strategy. The Home Office guide says you should not depend on the fire and rescue service to evacuate people. The strategy must depend only on factors within your own control, though you should consult your enforcing authority when planning it. All staff, including agency and temporary staff, must be fully trained in the evacuation procedures for the premises. Our guide to what a fire strategy is explains how the design intent is handed on.

Common mistakes

The problems official sources describe are mostly about how the building is run and maintained rather than how it was drawn. The same few come up repeatedly.

  • Compartmentation or fire stopping failures that let fire or smoke spread in ways the plan did not expect, which may force early evacuation of more sections or all residents (NFCC)
  • Hose lines and firefighters wedging doors open, creating flow paths for smoke into unaffected areas (NFCC)
  • Staff and managers unsure of the emergency plan, which incident commanders are told to anticipate (NFCC)
  • An escape strategy that relies on the fire and rescue service to move residents (Home Office guide)
  • Evacuation times never tested under worst case conditions with the lowest staffing (Home Office guide)
  • A change in resident or patient dependency without a review of the fire precautions, which HTM 05-02 says is likely to change them significantly
  • Two extra care schemes reviewed by the LFB in 2020 where evacuation to ultimate safety was inadequate and there was too little detail on how residents would be evacuated if needed

Wales and Scotland

PHE applies across the UK but the guidance documents differ by nation.

PHE guidance by nation
NationHealthcareCare homes
EnglandHTM 05-02, 2015 editionApproved Document B Volume 2, with at least three protected areas per storey and no more than 10 beds each
WalesWHTM 05-02, first edition, based on the 2014 HTM 05-02Welsh Approved Document B, with at least three protected areas per storey and no more than 10 beds unless a suppression system is fitted
ScotlandSHTM 81 Part 1, version 5.0, October 2022Technical Handbook, non-domestic, with compartments of up to 1500 square metres split into sub-compartments of up to 750 square metres

In Wales, WHTM 05-02 (opens in a new tab) carries the same PHE definition, compartment numbers and sub-compartment triggers as HTM 05-02. Regulation 37A (opens in a new tab) of the Building Regulations 2010 requires automatic fire suppression where building work is the erection or material change of use of a care home, including care homes for children. The Welsh Approved Document B (opens in a new tab) says that with suppression, bedroom fire doors need not have self-closing devices, protected areas may hold more than 10 beds and bedrooms may hold more than one bed. Gov.wales also lists an amendment slip applicable from 20th December 2025. Check it before relying on these paragraphs. See our Wales page for projects there.

In Scotland, SHTM 81 Part 1 (opens in a new tab) says every storey containing bed-patient areas in hospitals should be designed for PHE. The Technical Handbook (opens in a new tab) sets a maximum travel of 64 m in residential care buildings and no sleeping room for more than four people. It says any departure should take a risk based approach with early consultation of the verifier and fire and rescue service. See our Scotland page for projects there.

Wherever the building is, PHE only works if the compartments, the staffing and the management plan are designed as one. Our fire strategy reports set out that evacuation strategy and the assumptions behind it for the people who will run the building.

Sources

This guide was written from these official sources. Check the current version before relying on any figure.

Common questions

More on this topic.

All fire strategy questions

In simultaneous evacuation everyone leaves the building at once. Under progressive horizontal evacuation only those directly at risk are moved, sideways into an adjoining protected area on the same floor. Others stay where they are unless the fire grows.

Keep reading

Related guides.

Talk to an engineer

Tell us about the building

Send us the drawings, the building type and the stage you are at. We reply the same day with a clear scope, programme and fixed fee.

  • 01Written in-house by the engineer who will defend it to the approver
  • 02Approved Document B, BS 9999, BS 9991 and BS 7974
  • 03Building Control and fire authority engagement handled for you
  • 04Projects of every size, across the UK

Request a quote

Same-day reply

Only used to reply to this enquiry.

We reply the same day.