BB100 is the government design guide for fire safety in schools, published in September 2007 and still the only edition. Approved Document B in England says it should be used for schools. The DfE Technical Manual of January 2026 says it is no longer required on projects using the DfE employer's requirements, which follow the manual's own fire rules instead.

Last reviewed
Reading time
15 minutes
Related service
Fire Strategy Reports
A modern school building with glass and brick

What is BB100?

Building Bulletin 100, Design for fire safety in schools, is a design guide showing how the life safety requirements of the Building Regulations can be met in a new school or an extension. It was published in September 2007 by RIBA Enterprises on behalf of the then Department for Children, Schools and Families and is still the only edition. The GOV.UK publication page (opens in a new tab) carries the PDF with a sprinkler risk assessment tool and a cost benefit analysis tool. It shows no update or withdrawal notice.

The bulletin says it is largely based on Approved Document B (opens in a new tab). Its Sections 3 to 8 give detailed design guidance that, if followed, will usually enable a school design to satisfy requirements B1 to B5 of the Building Regulations. Following it is not compulsory. A designer may take another approach, possibly based on fire safety engineering, as long as the design is shown to be at least as safe.

BB100 also covers property protection, noting that measures that satisfy insurers will generally be more onerous in some respects. Its property protection recommendations are printed on a blue background so they are not mistaken for life safety guidance. A school fire strategy report should keep the two apart in the same way.

Read the 2007 text with its date in mind. It cites the Building Regulations 2000 (now the 2010 Regulations), Regulation 16B (now Regulation 38), the Education (School Premises) Regulations 1999, the former DCSF and BS 5588. All of these have since been replaced, superseded or withdrawn.

Is BB100 still the guidance to follow in England?

The official sources now point in two directions. Which one governs a project depends on how the building is being procured. The table sets out each position with its date.

Where official sources stand on BB100 in England
SourceDateWho it applies toWhat it says
Approved Document B Volume 2, paragraph 0.14Current online version (GOV.UK page last updated 16th September 2026)Building work to schools in EnglandThe design of fire safety in schools is covered by BB100, which should be used. BB100 also contains provisions outside the scope of the Building Regulations
DfE page, Fire safety in new and existing school buildingsPublished 11th March 2014New school buildings in EnglandBB100 is the normal means of compliance with the Building Regulations for fire safety design in new school buildings
DfE Technical Manual, revision C0112th January 2026Projects in England under the DfE Construction Framework 2025 (the manual forms part of its employer's requirements) and other routes that adopt itThe use of BB100 (2007 version) is no longer required. Projects follow section 9.1 Fire safety of the manual instead
Revised BB100 consultation draftConsulted on from 27th May 2021 to 18th August 2021Proposed for all schools in EnglandNever published. As at 23rd November 2026 GOV.UK still says the feedback is being analysed

BB100 has not been withdrawn. Approved Document B still directs designers of schools to it and the DfE fire safety page (opens in a new tab) still calls it the normal means of compliance.

On a project procured with the DfE employer's requirements, the DfE Technical Manual (opens in a new tab) replaces BB100 with its own fire requirements. Its section 9.1 mirrors the structure of Approved Document B Volume 2 and applies to all new and refurbished schools and colleges on those projects. The manual sits on the GOV.UK page Design standards: employer's requirements (opens in a new tab), which applies to England.

The manual accepts a BS 7974 fire engineering approach as an alternative route where the Employer agrees. Every requirement in section 9.1 must still be met. The manual is normally reviewed every 12 months and the DfE can update it at any time. Confirm the basis of design and the current revision with the client at the start.

The 2021 consultation draft (opens in a new tab) followed a call for evidence that ran from 8th March 2019 to 31st May 2019. It is not in force and is not a basis of design.

Which schools and buildings BB100 covers

BB100 (2007) covers schools in England and Wales. It names nursery schools, primary and secondary schools including sixth form colleges, academies and city technology colleges, special schools and pupil referral units. Sixth form colleges designated as Institutions of Further Education fall under Approved Document B, with BB100 as useful supplementary guidance.

Approved Document B defines a school as a place of education for children between 2 and 19 years old. Schools are not listed among its purpose groups because the 2006 revision was drafted on the understanding that BB100 would cover them. BB100 says the purpose group will in most cases be 5 (assembly and recreation). Where residential accommodation is involved it will be 2a.

The 2007 text does not name free schools, independent schools or early years settings other than nursery schools. It does not cover the following buildings and tells designers to use Approved Document B for them.

  • Buildings which include residential accommodation
  • Buildings with a top floor higher than 18 metres
  • Buildings with a basement deeper than 10 metres
  • Car parks, including those that form part of the school building

Boarding accommodation needs care in England. The note to Regulation 7(2) in Approved Document B confirms that rooms for residential purposes include dormitories in boarding schools. A boarding building with a storey at least 18 metres high therefore falls within that regulation. On its projects the DfE Technical Manual goes further. It applies all parts of Regulation 7 to any school building at least 18 metres high and any residential school building at least 11 metres high.

What the 2007 bulletin contains

Sections 1 and 2 cover scope, legal requirements, sprinkler policy, property protection, arson and fire safety management. Section 3 gives a design overview and Sections 4 to 8 take requirements B1 to B5 in turn.

Section 3 lists the places of special fire hazard found in schools. They are storage spaces, cloakrooms, laboratories and technology rooms, kitchens, ICT areas, corridors and circulation areas, temporary and relocatable accommodation and boiler rooms.

On alarms, BB100 says a category M system will generally satisfy the Building Regulations. It recommends a category P system for property protection unless the school is occupied at all times. The DfE Technical Manual sets a higher baseline on its projects with an L2/P2 system monitored by a manned alarm receiving centre 24 hours a day unless the building is continuously occupied.

BB100 notes that some pupils with special needs use larger wheelchairs and mobility aids. That affects door and corridor widths beyond those required by Approved Document M. Refuges need space for attendants too.

Travel distances, exits and stairs

Means of escape shapes much of a school layout. BB100 sets maximum travel distances by type of space, with a shorter limit where escape is possible in one direction only.

Maximum travel distances from BB100 (2007) Table 1. The DfE Technical Manual (January 2026) Table 28 gives the same figures.
SituationEscape in one direction onlyEscape in more than one direction
Places of special fire hazard9 metres18 metres
Areas with seating in rows15 metres32 metres
Areas not listed above18 metres45 metres
Ground storey of small premises with a single exit27 metresNot applicable

Where the layout is not yet known, both documents take the direct distance as two thirds of the travel distance. The DfE manual differs on one point. Science laboratories, studios and science preparation rooms, excluding chemical stores, need not be treated as places of special fire hazard for travel distance. For existing buildings BB100 notes that the fire risk assessment guidance lets these distances lengthen or shorten by about 30 to 50 percent for low or high risk.

BB100 Table 3 links exits to occupancy. Up to 60 people need one escape route or exit, up to 600 need two and more than 600 need three. A single route is acceptable where the storey exit is within the one direction limit and no room in that situation holds more than 60 people. A storey of no more than 60 people may also have a single route. On DfE projects the number of exits follows Approved Document B Volume 2 Table 2.2.

Exit widths in BB100 Table 4 are 750mm for 60 people, 850mm for 110 and 1050mm for 220. Above 220 the width grows by 50mm for each additional 10 people or part of 10. Corridors serving more than one or two teaching spaces should be at least 1.8 metres clear, at least 1.9 metres in new schools and 2.7 metres where there are lockers.

BB100 says dead end corridors should not be included in new buildings. The DfE manual limits the occupancy off an unavoidable dead end to 60 people. Very young children move more slowly than older children and adults. BB100 asks designers to consider direct access to an external place of safety from their classrooms.

BB100 says single stairways should ideally be avoided in new buildings. It allows one from a basement with a single route or in a building with no storey over 11 metres where every storey may have a single route. In that case storeys above the first floor should be occupied only by adults and the first storey should hold no more than 120 pupils plus supervisors. The DfE manual is stricter. Multi-storey buildings need more than one internal stair from every part of every storey, external escape stairs are not accepted in new buildings and evacuation lifts are required for people with mobility needs.

Occupancy figures for school spaces

Exit numbers and widths depend on how many people each space is designed to hold. Classrooms use their maximum design capacity, such as the number of seats. Other spaces use a floor space factor in square metres per person.

Occupancy figures from BB100 (2007) Table 2 and the DfE Technical Manual (January 2026) Table 29
SpaceBB100 Table 2DfE Technical Manual Table 29
Classroom, lecture room or study roomMaximum design capacity (for example the number of seats)Maximum design capacity
Dining room0.9 square metres per person0.9 square metres per person
Assembly hall or main hall0.45 square metres per person (assembly hall or dual purpose area)0.45 square metres per person (main hall or multi-purpose hall, also used for examinations)
Sports hall not used for assembly or examinations5.0 square metres per person5 square metres per person
Store room30.0 square metres per person30 square metres per person
Office6.0 square metres per person6 square metres per person
Staff room1.0 square metres per person (staff common room)1 square metre per person (staff social room)

Under the DfE manual the design occupancy normally comes from the project's schedule of spaces. The hall factor often drives exit design. Take a hypothetical hall of 270 square metres used for assembly. At 0.45 square metres per person it holds 600 people and BB100 Table 3 gives it two exits. Add a little more floor area and the hall needs a third.

Sprinklers, compartment sizes and property protection

BB100 notes that sprinklers are not a requirement of the Building Regulations. It records the DCSF policy announced on 1st March 2007 that all new schools should have sprinklers except a few low risk schools. The client is expected to ask for a sprinkler risk assessment as part of the employer's requirements whenever new schools or significant refurbishments leading to material alterations are planned. New schools scoring medium or high risk on the risk analysis tool are expected to have sprinklers.

The DfE Technical Manual of January 2026 is direct about its projects in England. Automatic fire suppression systems shall be fitted in new buildings and in major refurbishment of existing buildings in these cases.

  • Buildings that are at least four storeys high or over 11 metres high, measured from ground level on the lowest side to the floor of the top storey
  • Buildings with residential accommodation, such as boarding schools
  • All special schools, special colleges and alternative provision
Maximum compartment sizes in BB100 (2007) Table 9 and the DfE Technical Manual (January 2026) Table 31
BuildingBB100 without sprinklersBB100 with sprinklersDfE without suppressionDfE with suppression
Multi-storey800 square metres2,000 square metres2,000 square metres4,000 square metres
Single storey800 square metresNo limit4,000 square metres8,000 square metres

The manual lists exceptions. They include enclosed stairs and shafts, areas where water could be a hazard such as chemical stores and server rooms, outbuildings at least 10 metres away and temporary accommodation. Small two storey teaching buildings with no more than 120 pupils on the first floor are also excepted where the existing buildings have no suppression.

DfE systems are designed to BS EN 12845, with BS 9251 for residential accommodation. Where the system forms part of the life safety strategy it must be an enhanced availability system under Annex F of BS EN 12845, the type once called life safety. On DfE projects every floor is a compartment floor unless the building has suppression.

BB100 allows trade-offs for sprinklers only where the system qualifies as a life safety system. They are larger compartments, a halved boundary distance or doubled unprotected area, fire-fighting shafts up to 60 metres rather than 45 metres from a fire main outlet, mechanical smoke extraction in basements and 30 rather than 60 minutes of fire resistance in a low-rise building with a top floor under 5 metres. Claiming them for a system that only protects property does not meet BB100.

When BB100 was written, around 1 in 20 schools had a fire each year and nearly 60 percent of school fires were started deliberately. It notes that most insurers would recommend sprinklers for property protection. Design teams should consult enforcing bodies and property insurers early to balance the two.

Wales and Scotland

BB100 was written for schools in England and Wales. Wales still points to it, with funding rules that matter as much as the building regulations. Scotland has its own regime. Our Wales and Scotland pages cover projects in each.

BB100 and school sprinklers across England, Wales and Scotland
NationGuidanceStatus of BB100Sprinklers
EnglandApproved Document B Volume 2 and, on DfE projects, the DfE Technical Manual (January 2026)Approved Document B says it should be used. The DfE Technical Manual says it is no longer required on DfE projectsRequired on DfE projects in the cases the Technical Manual lists. Otherwise BB100 expects a sprinkler risk assessment
WalesWelsh Approved Document B Volume 2, paragraph 0.25Covers school design. Part B will typically be satisfied where its life safety guidance is followedA funding condition for Sustainable Communities for Learning new build school and college projects over 250 square metres or where significant remodelling takes place (April 2026)
ScotlandBuilding (Scotland) Regulations 2004 and the Technical HandbooksNot used. The April 2026 non-domestic handbook does not refer to itStandard 2.15 requires automatic fire suppression in school buildings, subject to its exception

In Wales the Welsh Approved Document B Volume 2 (opens in a new tab) points to BB100 at paragraph 0.25. The Welsh Government's Sustainable Communities for Learning business case guidance (opens in a new tab) of April 2026 says BB100 also applies to all school projects. Its sprinkler condition covers new builds over 250 square metres, whether standalone or an extension. Water mist systems should conform to BS 8458.

In Scotland, Standard 2.15 in the April 2026 non-domestic Technical Handbook (opens in a new tab) applies to a school building other than a building forming part of an existing school or an extension where installing suppression is not reasonably practicable. The guidance says a school building should have suppression for asset protection. It adds that an existing school's system should be extended into new accommodation on the site. Where an existing school is only being altered, the handbook says there is no need to install a system. That edition applies to building warrants submitted on or after 6th April 2026.

The fire strategy, management and handover

BB100 says a clear fire strategy report must be available on site and that it will incorporate the building's management principles. A design that relies on an unrealistic or unsustainable management regime cannot be considered to have met the Regulations. In a school that means testing each assumption against how the school really runs, from the lunchtime crush to evening lettings. Our guide to what a fire strategy is explains the document in more detail.

The Building Regulations impose no requirements on fire safety management. That falls under the Regulatory Reform (Fire Safety) Order 2005 (opens in a new tab), which extends to England and Wales. Article 9 requires the responsible person to make a suitable and sufficient risk assessment, review it regularly and keep a record. In England the Home Office guide Fire safety risk assessment: educational premises (opens in a new tab) supports that duty but does not apply to boarding school sleeping accommodation.

In maintained schools BB100 says responsibility is usually shared. The local authority usually holds the alarm systems and the structural fire integrity of the buildings. The governing body and the head teacher are responsible for running the school day to day.

At completion or first occupation the fire safety information must pass to the responsible person. BB100 calls this Regulation 16B, which is now Regulation 38 of the Building Regulations 2010. For a simple building it describes an as-built plan showing escape routes, compartmentation, fire doors, detectors and call points, sprinklers, smoke control, high-risk areas and management assumptions.

BB100 also flags two design details that often go wrong. Self-closing fire doors on stairways used as main circulation are likely to be wedged open or have their closers removed unless they have automatic release. Electronic access control on fire exit doors should fail open, not closed.

A good school strategy states the basis of design, the sprinkler position and the management assumptions in one place. Our fire strategy reports service does that for new schools, extensions and refurbishments. Where a strategy already exists, a fire strategy review checks it against the guidance the project now has to meet. Our schools and education page covers the sector.

Sources

This guide was written from these official sources. Check the current version before relying on any figure.

Common questions

More on this topic.

All fire strategy questions

BB100 is a design guide and a designer may take another approach, such as fire safety engineering, provided the design is shown to be as safe. Approved Document B in England says BB100 should be used for schools. The DfE Technical Manual of January 2026 says it is no longer required on projects using the DfE employer's requirements.

Keep reading

Related guides.

Talk to an engineer

Tell us about the building

Send us the drawings, the building type and the stage you are at. We reply the same day with a clear scope, programme and fixed fee.

  • 01Written in-house by the engineer who will defend it to the approver
  • 02Approved Document B, BS 9999, BS 9991 and BS 7974
  • 03Building Control and fire authority engagement handled for you
  • 04Projects of every size, across the UK

Request a quote

Same-day reply

Only used to reply to this enquiry.

We reply the same day.